0
4
Pitkin County Environmental Health Department
Permit for an Individual Sewage Disposal System
0405 Castle Creek Road, Suite 10, Aspen, Colorado 81611
Phone 970-920-5070 / FAX 970-920-5077
Permit # 4091 Parcel ID # 2467-252-00-590
Type of permit New(X ) Repair( ) Addition/Remodel to House( ) BARN w/ Caretaker
Name of Owner Barry Wehmiller Group/Last Chance Ranch
Street Address 1703 Lower River Road (formerly 300 East River Road)
Property legal description Lot 11 River Valley Ranch
Size of lot 27 acres Total square footage of the house 2,250 Barn
Water source
# of bedrooms in house # of offices, lofts & similar sized rooms in house
Caretaker unit Total square footage of the caretaker unit 871 sq ft
# of bedrooms in caretaker unit 1 # of offices, lofts & similar sized rooms in caretaker unit
Designed for what # rooms (list) 4 horse stalls+ toilet/sink for 6 employees+ 2 bedroom caretaker unit
Permit information
Designed by Church & Associates
Mailing Address 4501 Wadsworth Boulevard, Wheat Ridge, CO 80033
Perc rate 24 Profile hole depth 8 ft Depth to groundwater or bedrock >8 ft
Minimum Septic tank capacity 1488 gallons Minimum Absorption area 1166 sq ft
Septic permit approved per compliance with the engineer design and specifications dated October 27, 2004. Any
changes must be approved by this department and the design engineer 21i2l to them being made. Minimum
horizontal distances between components of the system and physical features shall conform to the Pitkin County
ISDS regulations.
Design is for one 2000 gallon, two compartment concrete septic tank with a Biotube pump vault in the second
compartment. There are five trenches of Infiltrator Quick4 t chambers, each trench 12 chambers long for a total of
60 chambers.
This department does not endorse any brand of products. This permit must be kept on-site during installation.
The engineer must do a final inspection of the installation and submit an as -built letter to this department. This
department must also be called for an inspection with a minimum of 48 hours advanced notice.
'Revegetation over the area of the field is very important for the functioning of the system. Pitkin County has guidelines that must be
followed to assure the plants that are introduced are appropriate for the conditions of the area. The use of native plants is strongly
Permit approved by: Date: l
Plans and specifications of the proposed individual sewage disposal system have been reviewed and are considered
satisfactory. Permission is hereby granted to the owner or the agent to perform the work indicated in accordance with the Pitkin
County ISDS Regulation in effect at the time of issue. This permit becomes invalid 6 months from the date that the permit was
issued unless system construction has commenced or an extension has been approved in writing by the Department.
As -built drawings must be included with this permit before the final approval will be issued.
Installer: SL"', Lr ._, z _ G� �� `-/✓-.-� L
Fit approval: d� c� CiL ����„c� Date: a— OS
M
ft
PITKIN COUNTY ENVIRONMENTAL HEALTH DEPARTMENT
APPLICATION FOR INDIVIDUAL SEWAGE DISPOSAL SYSTEM
0405 Castle Creek Road, Suite 10, Aspen Colorado 81611
Phone (970) 920-5070 Fax (970) 920-5077
Name of OWNER q - V✓k r /le, Gn/f n CC Ranch
Owner's Mailing Address 90,20 0/v
City, State, Zi / v / C 3 /0s Business Phones
Home Phone: E-mail Address: J
Primary Contact Person (all communication regarding this permit will go through this person)
Name
ni L/
-rt I /
Company
r
C rA
Contact Mailing
Address o
t La h
City, State, Zi
A r"'
Co /` / / Business Phone:
Cell Phone: j
j y �k
Fax: ), — 6 a E-mail Address:
Parcel ID # (available from assessor's office
at 920-5160 or at www.oitkinassessor.org)
Street address of property /7'OJ —vwe, lC/v"� K-( ( yUrr�tRfv ,Spo to
Legal Description: Lot ,Block Filing Subdivision Ver
Size of lot: i_— acres. Type of proposed structure: pg r /t
h
Total square feet of 4R � SV # of bedrooms (potential) in house
Caretaker Unit: Attached ( ) Detached ( )
Total area(sq, ft.) of caretaker unit # of bedrooms (potential) in caretaker unit
Permit is for: New Home (✓< Repair due to failure ( ) Remodel/Addition ( ) Emergency use ( )
Water: Private well (, <,Spring ( ) Stream ( ) Community/Public Water System ( )
If community system: Name of system
The fee for a ISDS application is $600 for a permit that takes 6 hours or less for the department to approve. If approval takes
longer than 6 hours, a rate of $100 per hour will be charged. The maximum fee is $1000. The basic fee of $600 is due at the
time of application. The remainder, if any, will be due in two stages: first, at the time of issuance of the ISDS permit; second,
before final approval of the ISDS permit.
Application for an individual sewage disposal system is hereby submitted. I hereby certify that the above information is true and
accurate and that I have provided true and accurate information on locations of all existing and proposed wells, contour
intervals, buildings, property lines, ditches, slopes, waterlines, springs, suction or irrigation lines, drinking water cisterns, drain
tiles, irrigation ditches, lakes, water courses, streams, floodplains, dry gulches, and existing septic systems. I hereby certify
that any such features not shown on attached site map are not present. Issuance of the permit does not imply the approval of
any other permit required for construction pursuant to Pitkin County codes. No construction may be undertaken until all
approvals and permits have been obtained.
The Pitkin County Environmental Health Department, Pitkin County and employees of these agencies will be held harmless
should the individual sewage disposal system fail or malfunction. The permit to construct is issued on information submitted by
the applicant or his/her representatives. The owner a s f II r onsibility i e of failure of the system.
Signature of applicant Q t ! Date
Received by Receipto� Date
J s
GNsdslisds appli6isdsapp Rev050103.doc �'
Name: V
ParcelID#:
Pitkin County Environmental Health Department
Contact Log Sheet
Comments / Action to be Taken
1 GL
0
0
PITKIN COUNTY ENVIRONMENTAL HEALTH & NATURAL RESOURCES
DATE: 16 IS I OS
Send to:—\al% !- 'vrvl�
Fax Number: 9,, - 6'% -6
CC: 3A,-Vo�A -� As��A6-1�
CC Fax Number:
From: A \ C �&�/] �Z
Phone Number: qab _SD- -7
Number of Pages, Including Cover:
❑ URGENT ❑ REPLY ASAP ❑ PLEASE COMMENT ❑ PLEASE REVIEW H FOR YOUR
INFORMATION
COMMENTS:
VNOL'SL"
Pitkin County Environmental Health and Natural Resources
0405 Castle Creek Road Suite #10, Aspen, CO 81611
Phone (970) 920.5070 1 Fax (970) 920.5077
Web site www.aspenpitkin.com/depts/12/
41
i 0
CHURCH & Associates. Inc.
ENGINEERS & GEOLOGISTS
December 20, 2004
Michael Fuller
do Bob Chapman
23400 Two Rivers Road
Basalt, Colorado 81621
Subject: Installation Observation, Proposed Fuller Barn
Tract 11, Aspen River Valley Ranch Subdivision RECEIVED
Last Chance Ranch
Pitkin County, Colorado
Job No. 16085W
Mr. Fuller,
JUL 2 9 2005
PITKIN COUNTY
ENVIRONMENTAL HEALTH
As requested, we observed the installation of the onsite wastewater system for the subject site on Novem-
ber 19, 2004. The system was designed under our Job No. 16085W, last revised October 27, 2004.
The system includes the installation of a 2000 -gallon, two-compartment, concrete septic tank with a pump
in a Biotube® pump vault and a gravelless chamber -trench drain field. The drain field was installed in four
trenches, each with one row of 15 Infiltrator® Quick4TM chambers for a total of 60 chambers and 588 i12
of infiltrative area. A concrete distribution box was installed to distribute effluent to the drain field. An as -
built drawing is included as Figure 1.
The components of the OW S design were installed in conformance with our plans and specifications. Final
electrical connections must be made by a licensed electrician. The construction foreman may activate the
pumping system at his discretion.
If there are questions or if we may be of further service, please call.
CHURCH & Associates, Inc.
Eric R. Burns
Field Technician
EOC/erb
3 copies sent, via Priority Mail
Copy to PCEHD, Attn: Nancy MacKenzie
Copy to Byrnes & Associates, Attn: Tim Byrnes, 90 Clay Lane, Aspen, Colorado 81611
_ DENVER 4501 Wadsworth Boulevard Wheat Ridge, CO 80033 www.goo-church.com
S 303.463.9317 Fax: 303.463.9321 Toll Free -1.877.248.3123
±25.56 AC S
TRACT 11 , -kormz.14 RIVER VALLEY RANCH SUBDIVISION
LAST CHANCE RA - H
PITKIN COUNTY, COLORADO
\
\
,
\ 588 SF OF INFILTRATIVE AREA IN FOUR
INFILTRATOR(TM) QUICK4(R) GRAVELLESS
\ CHAMBER -TRENCHES. EACH TRENCH
HAS ONE ROW OF 15 CHAMBERS
FOR A TOTAL OF 60 CHAMBERS.---�, /
i
SCALE .
1"=20'
R
•1
2000 -GALLON, TWO-COMPARTMENT,
CONCRETE SEPTIC TANK WITH A/
BIOTUBE(R) PUMP VAULT IN \\
THE SECOND COMPARTMENT.
y\100,
o
' \ 2' 'PURE CORE'
/ PR SED BARN WITH \
\ 4 HORSE STALLS \
\\ AND I -BEDROOM
\ APARTMENT 4' SEWER LINE WITH CLE
EXISTING
WELL
JOB NO. 16085W
AS -BUILT DRAWIN/
12/20/04
FIGURE 1
PIT'KIN ENVIRONMENTAL HEALTH DEPARTMENT•
ISDS DESIGN CALCULATIONS
QUICK 4 SIZING
Owner's Name Parcel ID #
House Size (sq. ft.) (75 gpd, 100 gpd, or 130 gpd)
Number of Bedrooms in Main House
Number of Offices, Libraries, Studies, Similar -sized Rooms in Main House
Number of Bedrooms in Detached Caretaker unit
Number of Offices, Studies, Similar -sized Rooms in Caretaker Unit
(If the caretaker unit is ATTACHED, treat as if part of main house.)
Average Daily Waste Flow 680
State Review Required? no
Perc Rate � (T)
Design Flow (Q) = # potential bedrooms X 2 people/ bedroom X gpd X 1.75
Q= 1190
Minimum tank capacity 1487.5 gallons
Absorption Area (=Q/5 X SQRT perc rate)
A = 1165.9571 sq. ft. of absorption area required
75 gravelless chamber units without reduction
# of Perc Holes Required: 3
1 in every soil type? Spaced uniformly over proposed area?
A maximum: 50%
only if the lot size and soil conditions are optimal.
If a reduction is being proposed, describe why lot size and soil conditions are optimal:
QUICK q_gUSl ICh4 92
A = 582.97856 sq.ft with 50% reductioniRENCHES 816.16998 sq ft 30% reduction BED
59 gravelless chamber units with reduction 89 chamber units with reduc.
Type of system: []Absorption trenches OAbsorption bed a Gravelless chambers
aDry well aSeepage Pit DOther (type)
SETBACK FROM WELL
# of feet = 115.2
SETBACK FROM POND, STREAM OR IRRIGATION DITCH
# of feet = 65.2
SETBACK FROM DRY GULCH
# of feet = 40.2
FPCrI : 0 FRx NO. : 0c,629 2004 08=15RM P2
CHURCH & Associates, Inc.
ENGINEERS & GEOLOGISTS
October 27, 2004
Michael Fuller
do Bob Chapman
23400 Two Rivers Road
Basalt, Colorado 81621
Subject Subsurface Investigation and OWS Design, Proposed Fuller Barn
Tract 11, Aspen River Valley Ranch Subdivision
Last Chance Ranch
Pitkin County, Colorado
Job No. 16085W
Mr Fuller,
As requested, we have prepared a revised onsite wastewater system (OWS) design for the proposed
residence The revisions arc based on an increase in the living area square footage of the caretaker unit
above the bam Brom our latest revised design, dated September 15, 2004, under Job No. 16085W. The
subsurface investigation was performed on June 24, 2004.
SITE CONDITIONS
The property is in a rural residential area of Pitkin County, where OWS are required. The proposed drain
field area slopes approximately 5% to the southwest The drain field area has a full cover of native grasses
and weeds. Water is supplied to the site by an existing well located greater than 100 fleet to the southwest of
the proposed drain field area
PROPOSED CONSTRUCTION
A horse bam with four horse stalls, a powder room to serve up to six employees, and a one -bedroom
apartment with a 5ving area of 800 ftz, is proposed at the location presented on Figures J and 2. A structure
with a living area greater than 700 ft1 must be sized for a minimum of two bedrooms, The OWS was sized
based on 680 gallons per day (GPD) using Pitkin County Environmental Health Department (PCEM)
loading of 50 GPD per horse stall, 30 GPD per employee for a toilet and sink in the powder room, and 75
GPD per person per bedroom. The sewage loading with a peaking factor of 1.75 is 1 190 GPD. This loading
includes washing machines and garbage grinders
if additional fixtures in unfinished areas are possible, it is suggested that the OWS be constructed to handle
the additional loading. The installation of a properly engineered OWS to serve future build -out can be cost
effective
DENVER 4601 Wadsworth Boulevard Wheat nldae, CO 60033 www.goo•church.com
303,163.9317 Fax: 303.463.6321 TO rre6-1.677.246.3123
FROM • FPX N0. 0cj*29 2004 08:15RM P3
Revised OWS Desi6m
Job So. 16085W, 10/27/04
Page 2
SUBSURFACE CONDITIONS
A subsurface investigation was performed by digging four percolation holes, 29 to 40 inches deep and one
test pit at the locations indicated on Figure 1. Subsurface materials in the test pit consisted of I foot of
clayey, sandy topsoil, underlain by slightly clayey, silty sand to the maximum depth explored of 8 feet.
Ground water was not encountered. Percolation tests indicate percolation rates of 20 to 27 minutes per inch
(MPU. The average percolation rate is 24 MPI. Percolation data is included as Table 1.
RECOWi4ENDAIIONS
The installation must. include a septic tank, an effluent pump, and a graveness chamber -trench drain field at
the locations presented on Figure 2 The OWS design is based on an average sewage load of 680 GPD and
a percolation rate of 24 MPI. The installation must include one 2000 -gallon, two-compartment, concrete
septic tank with a pump in a Biotube® pump vault in the second compartment and live Infittrator"m
QuiWO chamber -trenches. Each trench must have one row of 12 chambers for a total of 60 chambers and
588 ftZ of infiltrative area. A now splitter basin, or equivalent, is required to distribute effluent to the field.
Pump specifications are included as Figure S.
Based on soil conditions and evaluation of risk of contamination of surface water and ground water, it is not
necessary to add 8 feet additional distance for each 100 gallons of wastewater per day of design now over
1000 gallons per day as specified in the table to prevent contamination. The 100 -foot separation between
the proposed absorption arca and the well is appropriate to prevent contamination.
Vehicle movement over the drain field area during construction should be kept at a minimum to
minimize compaction of the receiving soils. The bottom of the trenches should be scarified with a pick,
shovel, or backhoe bucket teeth prior to the addition of chambers.
The surface of the field should be seeded after installation of the fields. A native seed mix should be sown at
the drain field to revegetate the surface. These mixes do not require irrigation and develop a growth 10 to
15 inches high. No automatic sprinkler system should be installed over the trenches.
OPERATION AND MAINTENANCE
The owner must realize an OWS is different from public sewer service. The owner must be aware of
and assume responsibility for maintenance of the system. In the absence of a monitoring program, the
septic tank should be pumped every two years. Effluent filter and screened vaults, as applicable, are to
be cleaned during pumping There are daily considerations such as not putting plastic or other nonbio-
degradable materials into the septic system. Garbage disposal use should be minimized.
The backwash of a water softener may be harmful to the OWS. A separate drywell should be constructed
for the backwash waste, if a softener is installed. Chemically treated water from a swimming pool or spas
should not be introduced to the OWS.
LIMITATIONS
A contractor experienced in OWS installation should be hired for the construction. Our investigation,
layout, design and recommendations are based on data submitted. If subsurface conditions different from
those described in this report are encountered, we should be notified to evaluate the change on the proposed
cI
FROM • FR`: 1,10. 029 2004 08:16AM P5
40 jtLR-ised OW$ Dc91gn
Tob No.16085W,10l27/04
Page 3
be
d to
e the impact
performance ofethe OWS T6 countyandour 6 m must be coes this design, we ntacted upon ompletiontof he OWS on the
P
All construction is to be in accordance with the ISDS regulations. Pipe type and size, burial requirements,
septic tank construction, and other specifications, which are not depicted in our report, are to onform to
the requirements of the ISOS regulations The installer of the system is to have demonstrated knowledge of
the PCEHD ISDS regulations and requirements.
or if we may be of further service, please call.
Of/Sri
If there are questions
OQP O�
10
Sincerely,
�,�i 13172
CHURCH & Associates, Inc.,Z7.0
Review d by
ONA4E
Eric R. Burns Edward O. Church,
P.E.
Design Technician
EOC/erb
z
Y copies sent
2 copies via FedEx to Byrnes & Associates, Attn: Jun Byrnes, 90 Clay Lane, Aspen, Colorado 81611
Faxed to Byrnes & Associates, Attn: Jim Byrnes, 970-923-6888
Faxed to PCEHD, Attn Nancy MacKenzie, 970-920-5077
FROMFRX N0, 0 29 2004 08:16AM P6
*26.66 ACRES • SCALE
TRACT 11, ASPEN RIVER VALLEY RANCH SUBDIVISION 1" = 100'
LAST CHANCE RANCH
PrVN COUNTY, COLORADO
A
bb
TIE LOCATION OF EXSTNO AND PAOFOSED
IMPROVEMENTS :.MOWN IEREN MID Tlf WELL MD/Op'•:; •.,
ORAN FIELD LOCATIONS STAKED AT TME .ITE ARE
NOT TME PF,SIAT OF A IADPCRTY SUIVlT.
IMPROVEMENT LOCATIONS ME WT'ROANWTE. 17 LR
THE { OPERTY OIWER'S RESPONSIBILITY TO DEFINE
PROFERTY POIFvDARIES AM EW4M ALL UNS"E
IMPROVEMENTS ARE LOCATED WITHN THE PLATTED
SITE AND DDT OF INMPROPMATE CASEMENTS. ALL
SETARATgN DISTANCES ARC TO PE VERIFIED P" TD
EXCAVATION.
o�jr
WSTINO
m /
\. \
RESIDENCE
EXISTING DRIVEWAY
TEST PIT
PROPOSED MORSE BARN
EXISTING WELT- `��' WITN I-REDROOM APARTMENT
SITE PLAN AND LOCATION OF
JOB NO. 1 B0B6W PERCOLATION HOLES 10,27104
REVISED FIGURE 1
FROM: 0 F111 M* 0 29 2004 08:16AN P-1
1 *26.68 . ACRES C6
SCALE
TRACT 11. ASPEN RIVER VALLEY RANCH SUBDNOON 30'
LAST CHANCE RANCH
PMN COUNTY, COLORADO
\ \�\ \ \ %ftNCE
ZQ
. . ....... .
\OW SPLITT 8 SIN EOLIrVALEW)
SCTeA TO DRA- FPFJ-D
ZODO�,ALITCK AR I M\ENT
'A, A . M Mot: . . . . . . . . . . .
N��C RETE So WITH BIOTLOIE(R)
Pt AULI INI�Tlli SfCONO C ILTR T C AGFA
-C" I
OF
TMENT. IN FZ 4-r TM) GUICK401)
CRAVELLESS C
TRENCHES. E MIST
HAVE ONE ROW 2 CHAMBER'..
FOR A TOTAL 00 CH PS.
v TBACK TO
TIC TAW
0 •
.00 0
EX. ING
WUL\
\'` PROPOSED BARN Wlt ii. `� /
/. HORSSTALLS
AM i-86ROOM APARTMENT
OF ED OW,
ONO. 1`&86W
VENT PIPES (TYr)
PVC Pump LME
V SEWER LINE
WITH CLEANOUT
REVISED FIGURE 2
0
O
TYPICAL PLAN VIEW - N.T.S.
w SPLITTER BASIN
(OR EOJ!VA'1NT)
QUICK4(R) ENO CAPS
' TR J. 055FJtVATOH/
WENT PIPES
4' PVC HEADERS
2lNnLTItAT0R(TM)OUlCgK4�R)O
Y PVC PJM? LINE
A
O
TYPICAL CROSS-SECTION - N.T.S.
TOTAL - FIVE TRENCHES
nolra1mn24m•
t' SDR 35 PVC
FUR
BSERVATION/VFNT PIPE
GRAVITY PLOR
WITH CAP
BMA1�'(E
]JOE
w •�-=..w
1
E9Awnu
{' RX
I
==o= 1 .w
4n'E `�
MIN.
OR,�HA�`=
1.5 Ma
NFlLTRAT3R(IM) QUIM4(R)
i s.Re
amm.
EXTENT OF EXCAVATM
GRAVnMLES5 CHAMBER. 3' X {'
CALCULATIONS AND SPECIFICATIONS
DESGK CRITMA
INCH SPECIFICATIONS
TREAT/.ENT UNIT SPECPICATKINS
SAM - A HORSE SCALLS, 1 PO'AOER ROOM FOR 6 OAP:OYEFS, & 1 -BEDROOM KUMBER OF TRENCHES - 5
LENGTH OF EACH TR - 48 FEET. 17 CHAMBER
TOTAL MIMMUM CAPAgTY = 1.75 X q X (JO HOURS/24 HX%S)
APARTMENT, 800 SF
LOADING - q - (t • 60 GPD) + IS G 30 GPD) + (2 G 2 x
-HCH
75 CPD) - 680 GPD WIDTH OF EACH TRENCH = 3 FM. 1 CHAMBER
- 1486 GALLONS ✓
PERCOLATION TEST - L - 24 MPI /
TOTAL NUMBER OFF CKAM376 - 60 CHAMBERS I/
RECOMMENDATION: ONE I003 -GALLON, TWO-COMPARMEAT,
AREA - 0.75 x q . Vq t t) / 5 - 1165 SF •/
GONCRETE SEPTIC TANK MM A 80TUE(R) PUMP VAULT M
502 REDUCTION FOR CHAMBER-TRENCRM - 563 SF
THE SECOND COAPARMENT
DRAIN FIELD DETAILS
10/27/04
JOB NO.. lO0 W
REVS RGUEE 3-
M
l
2000 -Gallon, Two -Compartment, Concrete Septic Tank with Effluent Pumping System
0�
AULT INLET PORTS
CLEAR ZONE OPENING IN
LOW INDUCER
24' Dl A. PVC RISER WITH
FIBERGLASS GASKETED LID
ACCEPTABLE ALTERNATIVE
GROMMET(S) (BOND To
CARTRIDGE
WITH STAINLESS STEEL BOLTS
k!FILTER
TANK ADAPTER WITH
AND 2' INSULATION
-
RECOMMENDED ADHESIVE)orewoSystem
?4' DIA. PVC RISER WITH
1 �,p„�,d
PVC SPLICE BOX
M (BONDTO
SLOPE GROUND
W/CORD GRIPS
TAN 4 A
871 All AVDFA
AWAY FROM RISERS (TVP.)
CONDUIT SEAL
RECOMMENDED ADHESIVE)
SUREIOIA 01®011
_III—I
=1 I I—III— I—Ti—• .
COi1�UVT �0
E ..
DISCHARGE ASSEMBLY
971A-9014
CONTROL PANEL
FLEXIBLE HOSE
EFFLUENT DISCHARGE
(541) 49-449
INLET
1/4' WEEP HOLE
(50)
R BAFFLE
45 -29114
TANK ADAPTER (CAST OR BOLTED)
o LIQUID LEVEL
LEVEL CONTROL
FLOAT ASSEMBLY
__ft��nyy If 4,439,323 t 5.402,615
g'amign POW Amd"
1997, Orwm Sylr9rs. Im
DISCLOSURE: THE PRESIDENT OF CHURCH B ASSOCIATES, INC. IS A NON -PARTICIPATING OWNER OF SCG ENTERPRISES, INC. WHICH IS A LOCAL DISTRIBUTOR
CF ORENCO SYSTEMS, INC. PRODUCTS. THIS DRAWING WAS PROVIDED BY OSI AND HAS BEEN MODIFIED BY CHURCH FOR THIS PROJECT.
CHURCH a Assodatm hto. 10/27/04
4501 wro Bow d TYPICAL SEPTIC TANK WITH PUMP JOB NO. 16085W
Wheat Ridge, Colorado I REVISED FIGURE 4
I
AULT INLET PORTS
CLEAR ZONE OPENING IN
LOW INDUCER
THE BAFFLE IS AN
SI EFFLUENT PUMP
ACCEPTABLE ALTERNATIVE
CARTRIDGE
TO PVC TEES
k!FILTER
RAIN PORT
IOTUBEOPLPIP VAULT
__ft��nyy If 4,439,323 t 5.402,615
g'amign POW Amd"
1997, Orwm Sylr9rs. Im
DISCLOSURE: THE PRESIDENT OF CHURCH B ASSOCIATES, INC. IS A NON -PARTICIPATING OWNER OF SCG ENTERPRISES, INC. WHICH IS A LOCAL DISTRIBUTOR
CF ORENCO SYSTEMS, INC. PRODUCTS. THIS DRAWING WAS PROVIDED BY OSI AND HAS BEEN MODIFIED BY CHURCH FOR THIS PROJECT.
CHURCH a Assodatm hto. 10/27/04
4501 wro Bow d TYPICAL SEPTIC TANK WITH PUMP JOB NO. 16085W
Wheat Ridge, Colorado I REVISED FIGURE 4
I
Pump Selection for a Non -Pressurized System
Input Parameters
0.0 feel
Design Flaw Rate
30 Wm
DistnbNchg Valve Model
None
Lift to Discharge
20.0 feel
Transport Length
75.0 feel
Transport Line Size
2.00 inches
Transport Pipe Class/Scnedule
40
Discharge Assemtify Sue
1.25 inches
Flow Meter
None incres
'Add-on' Friction Losses
U 1en
Head Loss Through Distributing Valve
0.0 feel
Head loss in Transport Pipe
11 feet
Head Loss Thmugh Discharge
45 feet
Head Loss Through Flow Meer
0.0 feet
'Add-crh' Frictron Losses
0.0 leer
Total Flow Rate 30.0 gpm
TDH 25.7 feet
Job No. 16065W
Revised Figure 5,10x27/04
B
12—
Net Discharge, gpm
Ca
Irene Systems*
IncaCcraled
Al f AMM AY AVNJF
SU-IiEHI1fl, OFECON
97579
•
TOLL FRff
7
X1396 -9&t7
ci
TELEPHONE ..
CA11454W
FAGSMU
C,n1uB IDBa
NYIW.01Yr1C0.CVT
J
m
SECTION VIEW
SIDE VIEW
INFILTRATOR(R) QUICK4(TM) CUT SHEET
•
9
N
ID
N
m
m
CD
m
mD
3
FROP1
�y
Fi : N0.
0 29 2004 08:18RM P12
TABLE 1 - PERCOLATION TEST RESULTS
Tract 11, Aspen River Valley Ranch Subd. DATE OF TEST: 6/24/04
Pitkin County, Colorado
TP -1:
2-1 !Topsoil, sand, clayey, moist, root zone
1 -8 Sand, silt ,all htl cls a ,moist, red, with occasional cobbles
NO GROUNDWATER WAS ENCOUNTERED WITHIN EXCAVATION
INTERVAL AVG.
DEPTH TIME DEPTH DEPTH CHANGE, PERC,
HOLE HOLE
NUMBER OF HOLE, INTERVAL, START, END, (INCHES) RATE PERC.
(INCHES) (MINUTES) (INCHES) (INCHES) (MPI) RATE,
IMPII
2 31 10
4.50
5.13
0.63
16
10
4.00
4.50
0.50
20
10
3.38
4.00
0.63
16
10
4.00
4.38
0.38
27
10
4.38
4.75
0.38
27
10
4.75
5.13
0.38
27 27
JOB NO. 16085W
FPDrl : • FAX N0. : 01029 2004 08:18AM P13
TABLE 1 - PERCOLATION TEST RESULTS
Tract 11, Aspen River Valley Ranch Subd.
Pltkln County, Colorado
TP•1:
tan} daerrinllnn
DATE OF TEST: 8124/04
0 - 1 To soil sand, clayey, moist root zone
1 -8 i1band, silty,611ghtly clayey, moist rod, with occasional Cobbles
NO GROUNDWATER WAS ENCOUNTERED WITHIN EXCAVATION
HOLE DEPTH TIME
DEPTH
DEPTH INTERVAL
AVG.
HOLE
HOLE
OF HOLE, INTERVAL,
NUMBER
START,
END, CHANGE, PERC,
(INCHES) (MINUTES)
(INCHES)
(INCHES) (INCHES) RATE
RATE,
(MPI)
JOB NO. 16085W
I�iliil!•
JOB NO. 16085W
0
17
0
--
]
t
o
9g
Z
W z
UZ
Z Q
2m
LUU)
1/�/)i1
< O
2
PERMIT SET
ai MMlpb. ub, wmp•�bb N Nb Mwb
>�.P ba.V.Uk w.MMM'
tlbMSRpMMI.Yp W p..bblb
mrMvs.rC M.Mw
'Mlb bN.bw YW W pw.MomwwMC
dmwW.NbbM �b.wMybl M✓
.M4np MMf4FCOnvbmrw.yl-.bM p
M.uY
PROJECT NO: 21009
DRAWN BY: EE
CHECKED BY:
ISSUE DATE: FEBRUARY 9.29a
FILE NAME:
-LOOR PLAN
A.101
• • o o_
Ow
q m
-----------------
6 p
Aay
::
r
ao �
A.102
904MM
April 19, 2004
Jim Byrnes
300 East River Ranch Rd.
Snowmass, CO 81654
ATTN: Jim
On April 16, 2004, a well test was conducted on a well on the Byme's (300 E. River
Ranch Rd.) Property. The following information was obtained;
Well Depth------------------------- Approx 60'
Casing Size--------------- 7 x 5"
Standing water level------------------- 23.23'
Total test time------------------- I Hour
Drawdown to ----------------------- 23.65'
Production is ------------------ 20 GPM
This test was conducted with Existing 114 Hp pump. The well recovered back to 23.23' in
! , Minutes. If you have any questions please call me, Raun Samuelson at 970-945-6309.
Sincerely;'
Raun E Samuelson
Samuelson Pump Co.
P.O. Box 297 • Glenwood Springs, CO 81602 • (970) 945-6309 • Fax (970) 947-9448
Water Systems • Sales, Service & Installation
Form No. OFFICE OF TH ATE ENGINEER •
GWS -25 COLORADO DIV ION OF WATER RESOURCES
818 Centennial Bldg., 1313 Sherman St., Denver, Colorado 80203
!3031 ARA 45A1
APPLICANT
MIN
LIC
WELL PERMIT NUMBER 235481 _
DIV. 5 WD 38 DES. BASIN MD
Lot: 11 Block: Filing: Subdiv: ASPEN RIVER VALLEY RANCH
ROBERT CHAPMAN
% PATRICK MILLER & KROPF PC
730 E DURANT STE 200
ASPEN, CO 81611-
(970)920-1028
APPROVED WELL LOCATION
PITKIN COUNTY
NW 1/4 SW 1/4 Section 25
Township 8 S Range 86 W Sixth P.M
DISTANCES FROM SECTION LINES
2695 Ft. from North Section Line
880 Ft. from West Section Line
UTM COORDINATES
ISSUANCE OF THIS PERMIT DOES NOT CONFER A WATER RIGHT
CONDITIONS OF APPROVAL
1) This well shall be used in such a way as to cause no material injury to existing water rights. The issuance of this permit
does not assure the applicant that no injury will occur to another vested water right or preclude another owner of a vested
water right from seeking relief in a civil court action.
2) The construction of this well shall be in compliance with the Water Well Construction Rules 2 CCR 402-2, unless approval
of a variance has been granted by the State Board of Examiners of Water Well Construction and Pump Installation
Contractors in accordance with Rule 18.
3) Approved pursuant to CRS 37-92-602(3)(b)(II)(A) as the only well on a tract of land of 38.30 acres described as lot 11,
Aspen River Valley Ranch division of land, Pitkin County.
4) The use of ground water from this well is limited to fire protection, ordinary household purposes inside not more than
three (3) single family dwellings, the watering of poultry, domestic animals and livestock on a farm or ranch and the
irrigation of not more than one (1) acre of home gardens and lawns.
5) The maximum pumping rate of this well shall not exceed 15 GPM.
6) The return flow from the use of this well must be through an individual waste water disposal system of the
non -evaporative type where the water is returned to the same stream system in which the well is located.
7) This well shall be constructed not more than 200 feet from the location specified on this permit. Qj $1Cy'I"7
APPROVED
JSG
State Engineer
14