HomeMy WebLinkAboutpitkin.eh.246734309001 (2012)CEH/NR C',3ITE WASTEWATER TREATM' IT SYSTEM (OWTS)
CONSTRUCTION PEra HT
7
76 Service Center Rd. Aspen, CO - 81611
Phone: 970.920.5070 Fax: 970.920.5374
Permit #: 002.2012.powt Parcel ID #: 2467-343-09-001
Permit Issued: ❑NEW ®REPAIR [IRE MODE L/ADDITION []TANK ONLY ❑FIELD ONLY ❑AMENDMENT
Owner(s): Kevin and Stephanie Heinecken
Property Address: 7030 E. Sopris Creek Road
Legal Description: Flanigan Lot Line Adj.
Size of Lot: 37
Size of Buildinq: 3294
Acres
Sq. Ft.
Detached Accessory Unit:
Size of Accessory Unit: _
®YES ❑NO
Separate ISDS 99075
Sq. Ft.
The system is designed for: 4 bedrooms (3 bedrooms + office), system NOT sized for art studio to be used as a
bedroom.
Designed By: Sopris Engineering
Phone #: 970-704-0311
Fax #
970-704-0311
Project #:
12019.01 Dated: February 1, 2012
Mailing Address: 502 Main Street, Carbondale, CO 81623
Email Address:
Perc Rate: 0.35 LTAR Profile Hole Depth: 7 ft Depth to Groundwater or Bedrock
Minimum Tank Capacity: 1125 gallons Minimum Absorption Area
Permit Conditions:
Greater than 7'
2571 sq ft w/ 20% reduction
This OWTS Construction Permit is approved on the condition of compliance with the engineer design as submitted with the application and the specifications
cited above. Changes must be approved by this Department and the engineer prior to construction.
This system was designed to replace the existing system which is experiencing saturated conditions and has failed. The
home can continue to be occupied, using the existing tank as a vault by plugging the outlet and pumping the tank
when full. Pumping records should be submitted to this office if field replacement takes more than one month from
the issuance date.
The existing 2000 gallon tank from the original system (ISDS Permit 99057) will continue to be used. An additional two
compartment 1500 or 2000 gallon tank with a .625 MicroFASTsystem and pump will be installed. The pump will dose to a
Geoflow Subsurface Dripline Dispersal field. Calculations for area are based on 0.35 LTAR and Geoflow sizing criteria. The
Geoflow wasteflow lines will be spaced 2' apart and wasteflow emitters will be spaced 2' apart. No part of the Geoflow field
should be placed under the driveway or in an area that may be driven on.
The existing field are from ISDS Permit 99057 may be abandoned or maintained for future use as an alternating system, once
the area has sufficiently dried out. A diversion mechanism to alternate between fields must be accessible from finished grade.
Alternating annually is recommended, and a record of alternating must be kept onsite.
This Permit must be kept on-site during installation. The engineer must do a final inspection of the installation and submit an "as -built" letter to this
Department within 30 days of the final inspection, unless a longer period of time has been agreed upon, in writing. This Department must also be called for
the final inspection with a minimum of 48 hours notice.
Minimum horizontal distances between components of the system and physical features shall conform to the requirements of the Pitkin County OWTS
Regulation.
This Permit is conditioned upon the property owner(s) providing for regular inspection, cleaning, and maintenance of the system by qualified personnel, in
accordance with the manufacturer's recommendations and the requirements of the Pitkin County OWTS Regulation. Issuance of this OWTS Construction
Permit does not constitute a guarantee, warranty, or representation by the Department that the system will operate properly or will not fail.
THIS PERMIT IS EXPRESSLY CONDITIONED UPON COMPLIANCE WITH ALL REQUIREMENTS OF THE PITKIN
COUNTY OWTS REGULATION, INCLUDING BUT NOT LIMITED TO THOSE CONDITIONS SPECIFIED ABOVE.
Plans and specifications for the proposed OWTS have been reviewed and are considered satisfactory. Permission is hereby
given to the property owner(s) to perform the work indicated in accordance with the Pitkin County OWTS Regulation. This
Permit will expire 1 year from the date of issuance unless construction on the system has commenced. An "as -built" drawing
must be submitted and approved by EH before final approval of the system will be issued.
Issued By: l ���� _ L (� Date: _ Expires: 3/20/12
Installer:
License #:
Reactivation Authorized by:
Final Approval Issued By:
Date:
New Expiration Date: fine pwfd
ONSITE WASTEWATER TREATMENT SYSTEM (OWTS)
CONSTRUCTION PERMIT APPLICATION
76 Service Center Rd - Aspen, CO •81611
Phone: 970.920.5070 Fax: 970.920.5374
Parcel IDS (available from the Pitkin County Assessors Office
970-920-6160 or atwww.pitkinassessor.org):
Company:
Purpose of Permit. ❑ NEW REPAIR DUE TO FAILURE ❑ REMODEL/ADDITION ❑ TANK ONLY
❑ FIELD ONLY
Cost of System Repair or Remodel/Addition (approximate):
Business Phone:
Property Address:
o So ver s r�
Email Address: ..
Lol Bkxk: Filing: / Subdivision: �1
/lilt/! aA% �iAJa /7j%rT
QQ
bit 7 T T 2
Property Owner(s)': Email Address:
aiaJrerV vid fJ �►r
Owners Mailing Address: Ciry, State. Z p:
J i �%
(,"�.�r Co
Home Phone Bust Phone
�-7 rZ -- 1 i 2.1-0
'Contact infotmation mus be provided tar the owner signing this application.
Pnmary Contact Person/Applicat �(d not owner):
r
i
Company:
Contact/ t Mailing
r
City, State, Zip:
Cell
Business Phone:
Fax Number: Z _
i
Email Address: ..
Building Permit # (if applicable):
Lot Size (in acres):
37* rtG
Size of Building (square feet): Number of Potential Bedrooms:
Detached Accessory Unit?r Size of Accessory Unit (square feet):
iJ rES ❑ NO
Number of Potential Bedrooms In or Fixture List for the Accessory Unit:
S r csti.�.r` O wTI
Water Source:
RNATE WELL ❑SURFACE WATER El SPRING ❑COMMUNITY/PUBLIC WATER SYSTEM. .
Name of Community/Public Water System (if applicable): -
Engmpenng Firm: / Job Number. Phone Number. Fax Number.
Mali Address: City, State, Zip:
GL ..w+ XA. e -o
PLEASE READ BEFORE SIGNING: "
I certify that the above information is complete and accurate and that I have provided complete and accurate information in all of the documents
included in my application package. 1 acknowledge that EWNR may revoke any permit 1 am Issued if my application Is found to contain any
inaccurate, false, or misleading Information. I understand that no construction may be undertaken on an OWTS until an OWTS Construction Permit is
issued.
Owner Signatur Vired- Date. " /Z/
C
Applicant &9%0[M
I f _ �/ � Date 'Z, 2— i -L.
AGENDA ITEM SUMMARY
March 15, 2012
TO: River Board
FROM: Carla Ostberg, Pitkin County Environmental Health Department
SUBJECT: Financial Assistance for Onsite Wastewater Treatment System (OWTS)
Replacement
Introduction: This summary is intended to generally inform the Board of the effect of
failing OWTSs, commonly referred to as septic systems, on the environment and public
health, as well as to alert the Board of a current situation having the potential to negatively
impact the environment and public health in the Capitol Creek drainage.
"Wastewater", also known as sewage, is defined in the Pitkin County OWTS Regulation as a
combination of liquid wastes that may include chemicals, household wastes, human
excreta, animal excreta, other animal or vegetable matter in suspension or solution, and
that is discharged from any building, dwelling, or other establishment.
Pitkin County has approximately 3000 parcels that fall outside of a sanitation district,
relying on OWTSs to treat their wastewater. Malfunctioning OWTSs contribute to non -
point source pollution and negatively impact water quality. Non -point source pollution
differs from point source pollution in that the pollution is not coming from a single source,
such as a factory. Non -point source pollution comes from the cumulative effect of day to
day activities including road maintenance, fertilizer application, and use of OWTSs. The
impact of non -point source pollution is often difficult quantify in the same way pollution
from a point source can be identified and measured.
In the last several years, the Pitkin County Environmental Health Department has seen an
increase in OWTS permits issued to address failures. Aging systems, improper
maintenance, and increased water use are all factors that are likely contributing to OWTS
failure rates in Pitkin County. However, failing OWTSs are not just a problem in Pitkin
County. Nationwide, contamination from septic systems and sewage overflows is an issue
of great concern.
American Rivers, an organization founded in 1973 to protect and restore the nation's rivers
and streams, posts the following information regarding the implications of sewage
contamination on the environment and public health:
"Sewage pollutes our waters with pathogens, excess nutrients, heavy metals, and other
toxins. It kills aquatic life and creates algal blooms that can suffocate fisheries.
Even worse, sewage carries pathogens that can end up in our drinking water supplies and
swimming areas. These disease -causing microorganisms cause diarrhea, vomiting,
respiratory, and other infections, hepatitis, dysentery, and other diseases. Common illnesses
caused by swimming in and drinking untreated or partially treated sewage include
March 15, 2012 C 0
Request for OWTS funding
gastroenteritis, but sewage is also linked to long term, chronic illnesses such as cancer, heart
disease, and arthritis." (w)Aw.americanrivers.org)
In February, I was contacted by the owners of a residence located at 703o E. Sopris Creek
Road. The OWTS serving the residence on the property, permitted and installed in 1999,
had failed and wastewater was coming to the ground surface. Capitol Creek is located
approximately 125 feet downhill from the lowest portion of the failed absorption area.
There are also several private drinking water wells in close proximity to the OWTS.
The cause of the failure is difficult to pinpoint as the system is relatively new, water use is
conservative, and maintenance of the system has been consistent; however, the receiving
soils are clay, meaning that it takes longer for any water or wastewater introduced to the
soil to absorb. The owners immediately addressed the problem by replacing the failed
system with appropriate technologies for the site and soil conditions.
I understand that maintaining and improving water quality and quantity within the Roaring
Fork watershed is one of several objectives of the Healthy Rivers and Streams fund was
established to attain. I believe that providing loans to homeowners needing to replace and
repair malfunctioning OWTSs aligns well with that objective. There are a number of other
states and counties that have established loan programs specifically to address OWTS
repair and replacement. A loan program of this type would benefit Pitkin County residents
while facilitating greater protection of our water resources.
Project Cost: $25,000
Requested Board Action: Approve funding a loan, based on the County Attorney's
approval of the loan agreement, for the property owners of 703o E. Sopris Creek Road to
offset the cost of replacing the OWTS serving this residence.
Attachments: Exhibit A: Google Earth location of property
Exhibit B: Photographs of failure after excavation
Exhibit B
Owl
lob
*Af
wo
NO
->o
co
o
.. M?ls R p40m
LEWIS 1041 HAZARD REVIEW SITE PLAN
TRACT 8, BEING A PORTION OF SEC. 34, T.8 S., R.86 W. AND
A PORTION OF SEC. 3, T.9 S., R.86 W., OF THE 6TH P.M.,
COUNTY OF PITKIN, STATE OF COLORADO
GRAPHIC'9CALE
(wear)
e u.x-rrort
°�►mv_a 'xJM wa'a"e v ° n it
mw.°mo°6COwCp a miwr 1 . 111. neeaoC° i`xY'r`m:+°r'
roxm w cww�ro�am *1
VICINITY MAP
1. xr a l-'.
ni m'"rorrrrWa."'"`K a Sr.`n"'ilzr«s'°.,11",ixn d "
.
a. x15Muin m�'i°°0ixfs�a[n i,[m�.uiiox w. bjj. �r
� rnw ro ,<M xx° roro i'ew.R. n ri!xix
rAa°Y�ixeac11�kou°iu an mMiOxa_Y°C°tl°�
xvaxce xiu axxw.°e w r ws � _1.--
a,. m xnm sr.rz
i. ewn �w+siara°1'i°°a,wnr°1y1 mxo,
,oc p
ILGLGCTTy
VICINITY MAP
1. xr a l-'.
ni m'"rorrrrWa."'"`K a Sr.`n"'ilzr«s'°.,11",ixn d "
.
a. x15Muin m�'i°°0ixfs�a[n i,[m�.uiiox w. bjj. �r
� rnw ro ,<M xx° roro i'ew.R. n ri!xix
rAa°Y�ixeac11�kou°iu an mMiOxa_Y°C°tl°�
xvaxce xiu axxw.°e w r ws � _1.--
a,. m xnm sr.rz
i. ewn �w+siara°1'i°°a,wnr°1y1 mxo,
.625 MicroFAST Treatment System wit
Item# Discharge Pump in 3rd Compartment
FAST.625-P
Top
View
Buhl RuMm
Sealant
Section
View
(4 Bedrooms)
X24• Pvc Rtaer
Minknw
HoW
Tank: 957"
*Meets ASTM C-9 227 spec
including C-9644-46 for resilient
connectors ___--------____-____.-_.-___-----
. 4000 psi concrete DWnp Specs knwt Dln" Blons
• Complete installation available in 95' Long x 8' Wlde Inlet outlet Length Width Height
some areas 58' below Inlet invert 5W 730 982' 78' 92'
Not apedy Nd WOW 1
l krat Side ' Odds Outlet � TOW Ltd Tank Toil
804 patlons 997 patlons 505 fledons 2.Q28 Ptlons 4.340 b 96.240 b 20,780 b
►.osratwe
water & (719) 395.6784 25005 Co, Rd 397
wwtowaw P.O. BOKS25
• VALLEY e PSysterm Floc (719) 395 -SM 8uer� VIft Co81291
P;M1�8'�', Inc. • Service W com
0
Goggtech
HEPWORTH-PAWLAK GEOTECHNICAL
February 1, 2012
Sopris Engineering
Attn: Paul Rutledge
502 Main Street, Suite A3
Carbondale, Colorado 81623
Subject: Laboratory Test Results
Dear Mr. Rutledge:
}i rover =Pa k ote-chnical, hw_
5 10 qty R oad 154
t t nwca xl S tipgs, (. k" � 1 '
Fa.x 970-9454454
eriaa�tc ia�ca�e�ti.ce�n
Job No. 112 015A
As requested, Hepworth-Pawlak Geotechnical, Inc. performed gradation and hydrometer
analysis testing on a sample delivered to our laboratory. The results are presented on
Figure 1.
If you have any questions or need further assistance, please call our office.
S incerely,
HEPWORT PAWLAK GEOTECHNICAL, INC.
g
Louis E. Eller
LEE/ksw
attachments Figure 1 — Gradation and Hydrometer Test Results
Parker 303-8414119 • (' )k)ra&-, prin#s 719.633.5562 • Silverrhome 970 -4b8 -141-i9
kri p••
/ .1 11
rrr•wrrrr�rr�w�
irwirrrrirrrr(iwrrrrrriirrrA•r
i ri i rrr v i i
i rir�rrwriiirrrws�iw�
11 1 1 11
���rrrrrrrrirrrr,w�-� i---
�r�rrrrirrrrrrr
i rr� rrrr i i i ��! w rrrrl rrr r rrr
rrr•r•a_iwrrrrrrr
w
w
i
irrrr�iirrrrri�rrrriii
iriiiiiirrrrrr_iiirrrA��•Irrrrirrrrrrr
1 r..��rrrr���wrrr�rrr��rrrr��wiiwrrrrr�
wrirrriiirrrrrrrr�.�iwr�rrr���rrrrirrr
i
i
i
rrrrrrirr•rA��i
rw•ir�rrr�iiwrrrrrr•�s_>�iirs•wi
rrrr�iii�iwirr��iirrrrrwrrrrr�irrrrrrr
ri i i i i
r�� ii i rrrrl
iliiiiw►.iwiwi
wrr�•rrrrirr�J.irr�rl���i rrrrrrr
rrrrrrr
irrrr�rr[ii rrrrrrr
---
rrrr
i! rrrr i i r� w r7 �! w rrr r
i r►� rrrr rrrr i i w rrrr rrrr i rrr r
irA��rrOr•irrrrr�
.1
rrr
rrr
iriiiirrr�r��wrrrr
ilriii�•/��wwiii
1 wrrrrrlrri�rrr/rrrrrrrrr�iirrr�ir��irrrrtrrrlrrrr
iii
i
w
iirrr'rrrrr
rrrrr rrA i i i ri rrr�
r•�rr�rrr�rrrrrr� rirr_•�ii�.wwlwi
iiwi�� rrrri•r�rrrrrrrrr
ilwil��r�
rrrrlwirr_ii�siirrrrrrr
it i w rrrri i� i� r� i i rrr r rr�
rrrrrrr
i
i
i
i�
i�iirrrrt�iiwiiirrrriir•rr•rrrrirrrr
rrr�wrr�
1 wl��•i�/�wlliiirri•i�l��irti�lrr_
i
i
rrrrl-rii
riii \�� �i
rr�iii irk �i
ri i i rrrrl r� �
i i i��
wir ��wwir�wir��
ri i ii f �
riiii/ rr�wwirrrriiir\r�iirrr
iwwiwiiw
rr�wiiii�rr[wirrrr
rrrwiiii�rrawirr�r
i rrrr w i i i i rrrr rrrr i rrri r
i� i i i rrrrl rrrr rr r� rrrr i rrr r
rrrrlrrrr
w wir11� wii� r� �� w rrr r
r
liiitr�
rrr
rrr
rrr
rrr
rrr 1
rrr
rrr
rrr
�
�r�rii�rrrl.ii�iirrrrl
rrrrrrirr��rr►/i
i
ii_ii•-iirrrriiiiirrrrwirrrrr�
iriirrr/�iiirrrr
1 r+..�����w������rir�w��iwr_��ww�r•rrr
r!!
wri i �� i rte!
iw�r�irrr�rrr rrrr
rrrrrrrrtrr/ir�iw�r�iirr• rrrr
rrr� i rrrrl iw! i i rrr r!
rrrriiii�r�rrrrirr�rrr�
.1
i��i��iiirr�rw�iirr�rr•r.w�wi
rrrrrrr
i
i���ii
wri�aiirrr�
rr��i•�iiirrrriiiirrrrt�r�wi
rrrrrrr
rrr�rrr�•iiirrrrr���irr�r rrr
�rrrriiwii���rrrrisr�
�
irirtli
irir�-ii
��ri•I�irrrrli�wwiiiilrrrrrrr�rrrrrrr
wrrrrlwrrrriiwiir•rA
rrr�rrrrrrrAiiiir��wirrrrrrr
rrl/�irrrrrrr
'
iri��iiiiiirr••riii�r�iirr�rrrr
1 i��r�w�wi
ir�rrr�r�r�r�wir�rrrr
1
i
irrrr/iw
irr��_i_i
rrrr� iiiiiwwirrrrlii�r�irrrrl�rrrr
iiirrrrwi
�•11� ii
iiirrrriirrrrrrr
rrrrii ii iss_ w i rrrr��
�
irrr�rr�w�ii.
irr�riwrrrri
��
irrr�rrrrwirr�rrrrirrrrwirrrr!
r���i � ��r�wirrrrrr�
a
•
irr�iii�wrrrrrrr�ii
w��iiiiiwrrrriw
� 1 iii/\�ii��/ww
i�liii•s_ii_i�i
rrr•r��iiiiiw�rrr�i
rrr/
i
r r arm rr r rrr� i i r�
�rrAiiirr�wiiiiirrrriirrrrrrr
ii��wwrrrrrrr
ii�r�wirr�rrrr
iiilr�ii�l�
iw r•rI� �i rrI•rrrr
iw ��i111/i Sri
� w i w i i w r� i i rrr r rrr
, 1
�
rr�.
rrr.riii�
rrs,friii�
rr rr•rii•��a_wrrrrwwrrrr.
Iarr�riiiirr/rwrrrr
r.��iiiiiwir!
rirr•lwrrrrrirr��wiiiwi�r�iirrrrrrr
iiwwir_i
i i
i�r�iii•rrrr
iswiilr•i irrrriirrrl rrrr
wrnrrirrrrarrr.rrr�
rrrrii iii rr/ wir�rrrr
i ii�rr rrrrirrrirrrrl
rrrri
��
ii•iiiiii•w�
iiiiiiirrrriiiii�r�rrrrrrrr�rrrr
i
:1 iw�iiiiirr•riiir/
rr���rrrr�iirrrrrrrrirrr����iir•�rrrr
i
rrrrrl rrr rrr� � i r�
wrrr�w iiia
riiirrr�w�iiwiii�r�rrrrii•rrrr
�iiii�r•/wwiii�'ii�r
ri i ii i i
iA iiirr�wrrrr
� w i i i i i� r� w i rr� r rrr
w rr�r rrr� iii �� rrrr i �_�
r_ ii! rrrrirr�rrrr
rrrrr•�rwirrrrr�
�rrr�
i rrrs v i i i rl r� i i rrr r rrr
rrrr rrrrliirrrrlliirrrrrrr
/
�
wri
rrrrl�
i�ii•iiiiiii
i�liiiiwiiii
wriirr.r♦iirrrriwirrrrirrr�wir•r�rrrrlirr�rrrr
wrrrrrlrrrirr�irrrAwwii
i
iriiiiiirrrrisiirrrrli
A♦i���iw
rrwiirrrrtwiw
�eiiii�iii
rrrriii ritr\Siwrrrr�
i � i ri/�r�ii�r r/�
irrr�rtr•wirrrrrrr
rrrrr•�rrrrirrrrrrr
ii�r�iirr�rrrr
wwr• r�wAA�rr�ri
rr�wi�rrr�
1
iiAiii`i�iiir�r_
i
iriiiiiiw
w
�rrrrirrwiwr•r�irrrrrrrrwiiw�rr•�irrrrrrr
f / wr��ir�w
ri i i i a i• i
riii iiwrrrr�
w��a_�•��iws.�ww�r�
r•�iir�rrrr
rrrr rrrr i i i a r� i i rrri r rrr
rrrr w iii r��irr�rrrrrrr
w iiir•�irrrrl�rrrr
1
11
// 11 11• 1 1 1
/ 11 •11 • f /
USDA GRADATION TEST RESULTS
100
SETBACK FROM WELL
# of feet =
50
SETBACK FROM POND, STREAM OR IRRIGATION DITCH
# of feet =
25
SETBACK FROM DRY GULCH
# of feet =
OWTS DESIGN CALCULATIONS - for Pitkin
USING LTAR
Owner's Name'. Parcel ID #.
House Size (sq. ft.) (75 gpd or 100 gpd)
75
Number of Bedrooms in Main House
Number of Offices, Libraries, Studies, Similar-sized Rooms in Main House
Number of Bedrooms in Detached Caretaker unit
Number of Offices, Studies, Similar-sized Rooms in Caretaker Unit
(If the caretaker unit is ATTACHED, treat as if part of main house.)
Average DailyWaste F 600
State Review Req ' ed? no
LTAR (T)rooms
X 2 people/bedroom Design Flow (Q) — ote ' edple/bedroom X gpd X 1.5
Q= 900
Minimum tank capacity 1125 gallons
Absorption Area (=B20 X 1.0/1317) A = Q x 1.0 loading/LTAR
A = 2,571 sq. ft. of absorption area required
A= 2,571 sq. ft. of absorption area required
Abs. Area w/ loading factor (B25) Trench Bed
Quick4 Trench
Quick4 Bed
Pipe and Gravel 2314 2571
234
261
Dosing 2W 2057
208
208
Chambers 1800 2314
182
234
Max Allowable 1286 1800
130
182
Secondary Treatment
Abs Area w/ out loading factor (B28) Trench Bed
Pipe and Gravel 2314 2571
234
261
Dosing 2057 2057
208
208
Chambers 1800 2314
182
234
Max Allowable 1286 1800
130
182
100
SETBACK FROM WELL
# of feet =
50
SETBACK FROM POND, STREAM OR IRRIGATION DITCH
# of feet =
25
SETBACK FROM DRY GULCH
# of feet =
Geoflow Subsurface Dripline Dispersal: Field Calculation
Job Description: 730 E. Sopris Creek - Heinecken 1730 E. Sopris Creek - Heinecken
Contact: Kevin Heinecken
Prepared by: Paul Rutledge, Sopris Engineering
Date: 1/31/2012
Please fill in the shaded areas and drop down menus below.
Note. This worksheet can be found in Geoflow's Design and Installation Manual
Dispersal Field as Dispersal Field as
S; -1a 7nne Mnitinle Innes
Number of Zones
1
2 zone(s)
A) I
Quantityof effluent to be disposed per day
900
450 gallons _/ da
B) 1HYdraulic
loading rate
0.3
0.3 gallons / s .ft. / da
C)
Determine total area required
3,000
1,500 square ft.
D)
Choosespacing between WASTEFLOW lines
2
2 ft.
D)
Choosespacing between WASTEFLOW emitters
2ft. (R
2 ft.
E)
ITotal linear ft.
1,500
750 each
F)
Total -number of emitters
750
375 each
G)
Select Wasteflow dripline
Wasteflow PC -1/2gph IWasteflow
PC 1/2 gph dripline
H)
Pressure at the beginning of the dripfield
20 psi t;'w
20 psi
1)
Feet of Head at the beginning of the dripfield
46.2
46.2 ft.
J)
What is the flow rate per emitter in gph?
0.53
0.53 gallons per hour
K)
Total flow for the area (gph)
398
199 gallons per hour
Total flow for the area (gpm)
6.63
3.31
gallons per minute
L)
Select pipe diameters for manifolds and submains
1
.5
inch
M)
Select Vortex Filter (item no.)
AP4E-.75F (0.75in.)
Consult factory
N)
Maximum length of each WASTEFLOW line.
For additional technical flow, pressure and flushing
data please refer to Geoflow's Design Manual
and WASTEFLOW hydraulics worksheet.
424
424
ft.
k,necK oetow to cnoose quantity WILL ieuyui Ui uauy uubcb
Dosing
Number of doses per day/zone:
Pump run time per dose/zone (minutes):
Pump run time per day/zone (hours):
Pump run time per day/all zones (hours):
12
12
11.32
11.32
2.26
2.26
2.26
4.53
minutes
hours / day
hours
Geoflow, Inc. Wasteflow Design Spreadsheet V.2003H 2/2/2012
Geoflow Subsurface Dripline Dispersal: Field Calculation
Job Description: 730 E. Sopris Creek - Heinecken 1730 E. Sopris Creek - Heinecken
Contact: I Kevin Heinecken
Prepared by: I Paul Rutledge, Sopris Engineering
Date: 11/31/2012
Please fill in the shaded areas and drop down menus below:
Note. This worksheet can be found in Geotlow's Design and histallation Manual
Worksheet - Field Design
Dispersal Field as Dispersal Field as
Single Zone Multiole Zones
Number of Zones 1
2 zone(s)
Quantityof effluent to be disposed per day 900
450 gallons / day
B)
Hydraulic loading rate 0.35
0.35mingallons / s .ft. / day
FA)
C)
Determine total area required 2,571
1,286 square ft.
D)
Choosespacing between WASTEFLOW lines 2
2 ft.
D)
Chooses acing between WASTEFLOW emitters 2 ft. 1
2 ft
E)
ITotal linear ft. 1,286
643 each
F)
ITotal number of emitters 643
321 each
G)
Select Wasteflow dripline Wasteflow PC - 1/2gphWasteflow
PC 1/2 gph dripline
H)
Pressure at the beginning of the dripfield 120 psi
20 psi
I)
Feet of Head at the beginning of the driptield 46.2
46.2 ft.
J)
What is the flow rate per emitter in gph? 0.53
0.53 gallons per hour
K)
Total flow for the area (gph) 341
170 gallons per hour
Total flow for the area (gpm) 5.68
2.84
gallons per minute
L)
Select pipe diameters for manifolds and submains 1
.5
inch
M)
Select Vortex Filter (item no.) AP4E-.75F (0.75in.)
Consult factory
N)
Maximum length of each WASTEFLOW line. 424
For additional technical flow, pressure and flushing
data please refer to Geoflow's Design Manual
and WASTEFLOW hydraulics worksheet.
424
ft.
Check below to choose quantity anct length of daily closes
Dosing
Number of doses per day/zone:
Pump run time per dose/zone (minutes):
Pump run time per day/zone (hours):
Pump run time per day/all zones (hours):
12
12
13.21
13.21
2.64
2.64
2.64
5.28
minutes
hours / day
hours
Geoflow, Inc. Wasteflow Design Spreadsheet V.2003H 2/2/2012
Geoflow Subsurface Dripline Dispersal. Field Calculation
Job Description: 730 E. Sopris Creek - Heinecken 1730 E. Sopris Creek - Heinecken
Contact: Kevin Heinecken
Prepared by: Paul Rutledge, Sopris Engineering
Date: 1/31/2012
Please fill in the shaded areas and drop down menus below:
Note. This worksheet can be found in Geotlow's Design and Installation Manual
Worksheet - Field Design
Dispersal Field as Dispersal Field as
cinalo 7nnP M dtinle Innes
Number of Zones
1 2 zone(s)
Quantityof effluent to be disposed per da
900 450 gallons / da
B)
Hydraulic loadingrate
0.35 0.35 gallons / s .ft. / da
PA)
C)
Determine total area required
2,571 1,286 square ft.
D)
Choosespacing between WASTEFLOW lines
2 2 ft.
D) I
Choosespacing between WASTEFLOW emitters
2 ft. 11 2 ft.
E)
ITotal linear ft.
1,286 643 each
F)
Total number of emitters
643 321 each
G)
Select Wasteflow dripline
Wasteflow PC - 1/2gph Wasteflow PC 1/2 gph dripline
H)
Pressure at the beginning of the dripfield
170 psi 20 psi
1)
Feet of Head at the beginning of the dripfield
46.2 46.2 ft.
J)
What is the flow rate per emitter in gph?
0.53 0.53 gallons per hour
K)
Total flow for the area (gph)
341 170 gallons per hour
Total flow for the area (gpm)
5.68 2.84
gallons per minute
L)
Select pipe diameters for manifolds and submains
1 .5
inch
M)
Select Vortex Filter (item no.)
AP4E-.75F (0.75in.) Consult factory
N)
Maximum length of each WASTEFLOW line.
For additional technical flow, pressure and flushing
data please refer to Geoflow's Design Manual
and WASTEFLOW hydraulics worksheet.
424 424
ft.
tnecK oetow ur cnerwc cluarrury arra rcrrgru Vr uauy UVZca
Dosing
Number of doses per day/zone:
Pump run time per dose/zone (minutes):
Pump run time per day/zone (hours):
Pump run time per day/all zones (hours):
12
12
13.21
13.21
2.64
2.64
2.64
5.28
minutes
hours / day
hours
Geoflow, Inc. Wasteflow Design Spreadsheet V.2003H 2/2/2012
t
NN
NN
y r w
_.'N
--4--4b
w
� ;.,
_ . �--
f "� � �
_ i"
�+� _ - r
�� •��'�.
-,. �.
" .�°
.^ �;Y
As
Aay
4 ~Y 4i
}^
K2
•�'�t � tom_
� t
Lo
v MFM— slow,
fe
' � f
T �VIA
�..
.� -
s,
v � � ��%
.�--
.�_ _
-_ � � � ---
-. ...:. _
�- �
4 .-� ,
� �..
;�
:' � / �
r /��,
1 ��
:x
d
•
a �
13
0.0
I
mop-*�-A
.�-r�I
�"
T� ,o
•� �
` l `�
-
;�M
f ` '� 1
iX'
yY
• ,� f: - - �' `� � fit'.. �� _.
LO
0
zr��-d
70 1
Ic
_ Am
G
W 4
TNUOUS MOST PRIOR TRACTOR
PTEF44RRR DOS GEDFIeA DR.IPL n FIELD NOTES
'
OO VI APPROXIMATELY R' LONER TWIN NOTED ON PUNS
RETURN MANIFOLD NVIN SHALL E A
RETURN
/
t- a
1. THE OWRNSOlS AND NOTES 9NDIN ON THE PUN INDICATE ~MI
ERSIING IXYNDf1VNn ARE SCiwAM aLY, BASED ON FIELD uGSUREMENIS
OBSERVATION. ACRAL COMPONENT INSTALLATOM LOCATIONS WILL RE FIELD
fRJ
i'
MEA. LENGTH, MOTHS AND SEPARATION DISTANCES FOR THE MR24E
LAYOUT. THE TOTAL LENGTH OF DRNIME LATERALS SHALL BE
DETERWNED PER THE INTENT OF TILE PUN THE PROPOSED OMS DESIGN 5 BY
$OpgIS ENON lw. LLC.
S. SAL. AU- SANITARY
TANKS INSTALL ONLY NIST ONES ON LOWNC TANKS. TRIOVAL ALL SANITANY
EASY INSPECTION AND MAINTENANCE
INSTALLED N A C.US. ARRAY TO B: DETENYRIED IN THE RE.,
m 9 ! NQ=
7. THE DINE NES ARE INSTALLED FROM ONE MANIFOLD WEN 1' PVC TEES. LEES AND W A POSITION ro ALLOW
OF TAMIL FROM THE TANK RISERS
2 THE DRWLMFS WALL BE INSTALLED N NARROW TRENCHES EXCAVATED
I. ALL MA. AND INSTALLATION SHALL CONFORM TO STATE AND COUNTY
RELATIVELY LEVEL FOLLOWING THE EIGBYNG GRADE CONTOURS THE
INDIVIDUAL SEWAGE DISPOSAL SYSTEM ISDS REGIUTWS
� U
a
t d
LL BE PLACED IN THE B' -IB' DEEP TRENCHES
GIRN.WE LATERALS WILL
OMER THE NATIVE SOL AND BACKFILLED Mini THE NATV£ SGL THE
2 IT IS THE REWONS WR OF THE CONTRACTOR TO CONTACT UTILITY LOCATORS
E W CONFORMANCE WIN M YANIEACTURES V/STALATON THE EFFLUENT FELT R SINAL BE MAINTAINED AND CLEANED WHEN THE TANK IS
.
a o o m
TRENCH BOTTOM AND SYT.'I SHALL E SCARIFIED AND/OR
AND U1LTY COMPANIES AS NEEDED FOR FIELD LOCATIONS OF UTILITIES PRIOR TOBACKE
2 m
Om
..
.5.:..
���W�'
E LEnRING OCCURS,
BACKEDS,
CONSTRUCTION AND EXCAVATION.
-
MTt ALL FIXTURES AND ORIS OWA MR FROM
BE INS ARE xA AND
UVN
FROM VWQILAR AND UVESTOCIE TRAFFIC E INSTALLED AND YAW7AIED ro AVGO SURFACE OR ptO1NDWATER FROM
t MAIN ALL TO AVOID
1 INSTALL THE 'WASTE FLOW PC IXxPLYNE' PRESSURE COMPENSATING
1 ALL GRAVITY SEMEN LINES TO BE 4' SOR-35. OR SCHEDULE 40 P.V.C. PIPE
+
% ANY POTENTIAL SURFACE DRAINAGE SHALL E RATED AWAY FROM ENTERING THE SYSTEM AND ro PREVENT LEAKAGE FROM THE SYSTEM. IN-HOUSE
UMOM FMTU AL. BE MAINTAINED PREVENT EXCESS WATER FROM
PRS SI
�.M
(�
ORPLWEs MTI EWrTm ON 7 [ENTERS EQUAL PRESSURE
UNLESS NOIID OTHERINSE ALL DRAWN SEVER ONES TO BE INSTALLED ON A
R. 11E ENTIRE DISPERSAL FIELD SURFACE YIISi BE RE VEfLTAIED 12 THE NSIM IATI N OF THE TREATMENT. DLSTRIBUnON AND CONTROL COMPONENTS
TO BE PROVIDED
�0Y
y
=INVENTION DYER THE ENTRE FIELD all. BE MAINTAINED.
2R GRADE LIES MAY BE STEPPED DOW BETWEEN 2E RARE. FITTINGS AT ALL
VERTICAL AND 11w ITA BENDS NOT TO EXCEED 4S. USE CLASS B SECOND.
1. GEOTECHNICAL EYADATIOTS AND INSPECiKNS BY THE
FIELD WI PRESSURE DOSED GED FLOW DRILIMM LAYOUT
4. DISPERSALRE
4. ALL PRESSURE LIVES TO BE SCIEDLLE 40 P.V.0 DE HDPE SOR-7 PINK UNLESS
ADDITIONAL
ENG94V MEL BE PERFORMED AS A BASES FOR THE FINAL DISPERSAL 1J. AT 711E DINNERS ALOE, P A AST,MANUFACTURESWWILL REPRESENTATIVEOEECNI ALL SERVICE
SEPTI: � LTA PRECAST. CULL PROVIDE TECHNICAL SUPPORT TO
OF ZMLOW GSPERSAL ARRAYS, AND DISTRIBUTOR PIPPING ro BE
NOTED OTHETtWSE PRESSOE I.me ro BE INSTALLED WITH A MNWY 1f
LUpE BY M ENGINEER M Q FOR NATAL STAGES O' CONSTRICIICI ro ON -SCE DURING CONSTRUCTION. ALL SEANCE SEPTIC AND/OB VALLEY PRECAST
DU
VERITY ASSUMPTIONS MADE FOR M ONS OESOx INSPECTIONS
OPTIMAL ION ONANCE. mmumpINSTADENLATION
PEND OETERYN T TO PRESERVE
AND TO PREgNVf IEC: TAl10N TO THE MAXWUY EXIEJIT
GLADE FOR DRAW BALL NO LOW POINTS OR DIPS ARE ACCEPTABLE ALONG
PRESSURE PPE RUNS AYE RELEASE MECUN915 REQUIRED AT ALL MOI POINTS
s 2 SOPRIS ENGINEERING HAS PERFORM SOIL PERCOLATION RATE TESTS N
PROPOSED AREA ME DISPERSAL FLED DBELOWNe ME
70 A' BELOW ME SURFACEPERFORMED
POSUKOT
PM9N.E
FITTINGS A. ALL VERTICAL AND NORZONTA BENDS NOT TO EXCEED 45'.
N P ro OECFAMNE THE SORB BE1AVIOt AND ACCEPTANCE OF TREATED
I. W'ASTENATER AT A SPECKED RATE 1. A CONTROL PANEL SMALL E INSTALLED BY A EEECCRCIOAN IN
COORDINAnCM NTH ME CECTRIC AL WE RECOMMEND 230 `ALT
/
^ NWIIWIM L THE ACTUAL LAYOUT OF THE DISPOWBA FIELD AND THE ASSOCIATED ELECTRIC SERVICE BE PROVIDED TO THE PIMP AND AERATION BLOWER
L NWALL THE SPECIFIED LENGTH OF I/2' DOMAIN WASTE FLOW PC
S ALL GRAVITY AND PRESSURE UNE TO E BID= AND BAIXFlIIm NTH SUITABLE
/ DMIN-M LATERALS AND MANIFOLDS WILL E DETERMINED IN THE FIELD THE POWER SUPPLY FOR THE PUMP. NR UNIT AND CONTROLS SHALL
AND APPROVED BY M E1GIIlER. CONSST OF S) 20 AMP DOUBLE POE CIRCUITS FOR THE PUMPS AND
(1) 10 AMP SNORE POLE CIRCUIT FOR CONTROLS. PANEL TO BE
T"' "' ♦ 4. PRIOR ro CO SIRUCTICN OF THE PERMITTED SYSTEM ME ENGINEER wSTALLED W LOBE OF STE ATH TREATMENT TANTE
corm WIM ow IYITIERS ON Y CENTERS THE ASSUMED LENGTH
SOIL GR CAS" ROAD BASF IN TRENCHES WTH UNDISTURBED STB
I'OEPOWN75 01W THE CONTRACTOR, ANSWER QUESTIONS RESOLVE Mr FROM THE, SERVICE PANEL. /0 A DISCONNECT SERVICE BOK LOCATED
DIT G10M DIRKN[ uTDEK SHALL E APPR0.NUl6r AS 9NOVW ON
TF[ RAN, THE GWLM LATERALS SHALL BE INSTALLED N AN ARRAY
OF NEAR PARALLEL LATERALS GENERALLY FOLLOWING THE CONTOURS
GRADE SOL OR COMPACT SUB MADE AS NEEDED. LOCATION OF BIURET PIPES TO
BE MARKED N THE FIELD.
r ENGINEER. SUPPLER. THE CONTRACTOR. ELECTRICIAN ANO TIE QUALIFIED TERMINATE IN PANEL WEN APPROPRIATE PHOS LNE CONNECTOR.
-
NSTAlER IS ESSENTIAL AND REQUIRED PRIOR ro NSTAUTICN OF THE
OMS COMPONENTS PRE CONSIA)C110N CONSIA.TATION INSPECTIONS AND 1 M SYSTEM QUALIFIED INSTALLER SHALL INSTALL ELECTRICAL DIRECT
CUTIN AREAS EAS OF TE FIELD STE LI ES TO BE INSTALLED AT
S ALL PVC RWG PE SHALL BE CUT WIN A PIPE CUTTER. U PVC IS PROHIBITED TO
-
E.E INCLUDED IN M SYSTEM COST. PUMP ASSEMBLIES 494CTM BOXES IN TIE RESPECTIVE RISERS OVER
M TREATMENT TAMIL INSTALL COLOR LVED WNES PEA
S OL
TMENTINSTALL
MIN. if DEPTH NOT TO EXCEED TY N NARROW IRENCKS TO AVOID
DISTMIBANM OF EXISTING VEGETATION TO 111E PRACTrA EVENT
SBI. E UM SEPARATION DISTANCE KTKM LATERALS IS
P09E TMINI
PREVENT ACCUYLV..YTIOM OF SHALL FILINGS IN THE PRESSURE DOSED SYSiFYi
ALL PVC TO E SOLVENT ADDED.
-
PERFORM STE NSPECIKNS OF M PERMITTED SYSTEM MARRING COMQIT SEAL NEM FUSER SPLICE BOIL ELECTRIAN TO COORDINATE W/
CONSTRUCTION AND PPONOE'AS-BAON T` DOCUMENTATIOF THE SYSTEM NSTAUER. FOR RECIRCULATIONASSEMBffS INSTALLATION
2 FEET HOWEVER THE SEPTON DISTANCE MAY BE VARY BASO ON
7. INSTALL A 7110 -WAY (SEAN CUT DIF M STANCE LINES FROM ALL BUILDINGS,
COMPLETE WE RECOMMEND INSTALLED OWS: _ C SURVEYED TO OBTAINGUNEDATAS-BUILT NTFORYAC IMPON. NT$ BE ows I)= cnrf RIA
VEGETATION. GRAM ANO OTHERE16S11NG CONDITIONS NTTIE
FIELD AREAS
AOB1710RIAL CEANOUT REQUIRE AT UPSTREAM GRACE BREAKS AND AT A YWRMI
TOE DISTANCE HONG ALL GRAVITY LINES.
w
L THE ORPLAE LATERALS BE ALSHALL INSTALLED TO PROVIDE A MINIMUMWMINIMUMd
8 ENE SEPTIC TANKS SIAL MWEERndIT AND INSTALLED LEVE ON COMPACTED
w
LI
IV pS5E7 O' M FIRST AND LAST EITHER FROM TIE SLIMLY AND
DIAMETER MAWOM SHA
RETURN MANIFOLDS RESPECTIVELY. THE I' DIAMETERD.
ROPE DOWN FROM THE
STALL
L
EMM THE TAMES E CERTIFIED AS WATERTIGHT BY 111E WtACEMEN
MID SEAM TARES SHALL BE TESTED FOR MWTER T04TNM AFTER PL ACfMEINT
TO TO INSTALL THE WATER RISERS AS
E INSTATED AT CON AND BRING A CON
NECESSARY ro CIRC ALL NEAND O ACCESS POINTS ro M FINISHED ORENCO SNEACE
ii •• W-IRMORNT LITERAL ro THE LY AND VAIN ro INSIDE S. THE
R THE SUPPLY REAM MANIFOLDS. 111E OMOE AL RECIRCULATION AND 009NG HARKS STALL HAVE ORNCO RISERS AS
OO VI APPROXIMATELY R' LONER TWIN NOTED ON PUNS
RETURN MANIFOLD NVIN SHALL E A
RETURN
IR VACUUM
,ty H SAPPILY ON O. INSTALL M, VACUUM BREAKERS TES IN THE
PLY MAM
MCIEST POINTSDL ON TE DISPERSAL FEED (OM M IERMWA ENDS OF B. A SANITARY BAFFLE TEES ARE REQUIRED ALL PRIMARY SEPTIC TARN N1E15
E TION
M MANIFOLD LIES} AND OUTLETS, (DO NOT INSTIL SANITARY BAFFIN
V
S. SAL. AU- SANITARY
TANKS INSTALL ONLY NIST ONES ON LOWNC TANKS. TRIOVAL ALL SANITANY
EASY INSPECTION AND MAINTENANCE
7
Gi
7. THE DINE NES ARE INSTALLED FROM ONE MANIFOLD WEN 1' PVC TEES. LEES AND W A POSITION ro ALLOW
OF TAMIL FROM THE TANK RISERS
OO ARES" ATTEND ADAPTERS AND COMPRESSON COUPLERS AS
Nom. 10. FOR PUP SYSTEMS. WE RECOMMEND ME INSTALLATION OFT OPENCO NIDI-TUSE
W
� U
a
L ALL INSTALLATION OF CIRPPLPET AND DPSMMY N MANIFOLDS SHALL. SCREEN VAILT FOR THE SPECIFIED RUMP ASSEMBLIESro E INSTALLED IN THE
TANK OR PUP BASIN. ONE FILTER SHOULD BE INSPECTED EVERY SX MONTHS
7
N IU e
n o
E W CONFORMANCE WIN M YANIEACTURES V/STALATON THE EFFLUENT FELT R SINAL BE MAINTAINED AND CLEANED WHEN THE TANK IS
C.i
a o o m
YIS TRUCTONS (SEE ATTACHED WTEiRIAL} PEFVQW LLT PUMPED OR AS NECESSARY. INSTALL A BITABLE EXiENSON ON
EASY ACCESS IN RISER
2 m
Om
J L THE DISPERSAL FIELD MUST BE GENERALLY LOCATED ON AN AS-PIAE T TFILTER HANDLE K NEEDED FOR
���W�'
x
C LL
SHALL THAT M SERER LINES, SEPTIC TANK AND
OE MR AND POSSIBLY WTI SLATS. THE
AE PON CTED it. THE CdIRE
FIELDS
POINTS. TIE FEEDS AL57 BE PROTECTED SHALL
-' FR RAR AT KEY QUID
<
U
MTt ALL FIXTURES AND ORIS OWA MR FROM
BE INS ARE xA AND
UVN
FROM VWQILAR AND UVESTOCIE TRAFFIC E INSTALLED AND YAW7AIED ro AVGO SURFACE OR ptO1NDWATER FROM
t MAIN ALL TO AVOID
p]
+
% ANY POTENTIAL SURFACE DRAINAGE SHALL E RATED AWAY FROM ENTERING THE SYSTEM AND ro PREVENT LEAKAGE FROM THE SYSTEM. IN-HOUSE
UMOM FMTU AL. BE MAINTAINED PREVENT EXCESS WATER FROM
PRS SI
�.M
(�
~ M i1FlD. ENTERING THE SEPTIC mml.
�#
R. 11E ENTIRE DISPERSAL FIELD SURFACE YIISi BE RE VEfLTAIED 12 THE NSIM IATI N OF THE TREATMENT. DLSTRIBUnON AND CONTROL COMPONENTS
TO BE PROVIDED
�0Y
y
WILL, NOMME WMIAL ASSEMBLY EOINPYENT AND MATERIALS
BY VALLEY PRECAST.
1. GEOTECHNICAL EYADATIOTS AND INSPECiKNS BY THE
ADDITIONAL
ENG94V MEL BE PERFORMED AS A BASES FOR THE FINAL DISPERSAL 1J. AT 711E DINNERS ALOE, P A AST,MANUFACTURESWWILL REPRESENTATIVEOEECNI ALL SERVICE
SEPTI: � LTA PRECAST. CULL PROVIDE TECHNICAL SUPPORT TO
FIELD DESIGN. ADDITIONAL INSPECTIONS AND RECOMMENDATIONS WILL BE ' CONSULTATION ro ME CONTRACTORS. INSTALLERS WO !PRECAST
ono WSTALI.Y NS THE
LUpE BY M ENGINEER M Q FOR NATAL STAGES O' CONSTRICIICI ro ON -SCE DURING CONSTRUCTION. ALL SEANCE SEPTIC AND/OB VALLEY PRECAST
DU
VERITY ASSUMPTIONS MADE FOR M ONS OESOx INSPECTIONS
Nu pLSTA1 THE IPGIYFNT SYSTEM AND PEAFGYRI
s 2 SOPRIS ENGINEERING HAS PERFORM SOIL PERCOLATION RATE TESTS N
PROPOSED AREA ME DISPERSAL FLED DBELOWNe ME
70 A' BELOW ME SURFACEPERFORMED
AT 2
H LO RATE DO THE SOL U' Mn srmWTn IT vrnPPeT �p � �a � �)
HYDRA ES F CONTROLLED
y, A SERIES OF COI1ROlID DOSED RKLTMTON LEST MAY BE PENFORMED oLMB1NYYMBY_ilNAA1L
N P ro OECFAMNE THE SORB BE1AVIOt AND ACCEPTANCE OF TREATED
I. W'ASTENATER AT A SPECKED RATE 1. A CONTROL PANEL SMALL E INSTALLED BY A EEECCRCIOAN IN
COORDINAnCM NTH ME CECTRIC AL WE RECOMMEND 230 `ALT
/
^ NWIIWIM L THE ACTUAL LAYOUT OF THE DISPOWBA FIELD AND THE ASSOCIATED ELECTRIC SERVICE BE PROVIDED TO THE PIMP AND AERATION BLOWER
/ DMIN-M LATERALS AND MANIFOLDS WILL E DETERMINED IN THE FIELD THE POWER SUPPLY FOR THE PUMP. NR UNIT AND CONTROLS SHALL
AND APPROVED BY M E1GIIlER. CONSST OF S) 20 AMP DOUBLE POE CIRCUITS FOR THE PUMPS AND
(1) 10 AMP SNORE POLE CIRCUIT FOR CONTROLS. PANEL TO BE
T"' "' ♦ 4. PRIOR ro CO SIRUCTICN OF THE PERMITTED SYSTEM ME ENGINEER wSTALLED W LOBE OF STE ATH TREATMENT TANTE
.. SHOULD E CONTACTED BY THE PRGJ= MANAGER/CONiRACT01t WELL N
ADVANTO PROVIDE ADEQUATE TIME TO DISCUSS IME STSTEY2 THE CONTRACTOR SHALL INSTALL OUOC JL SUPPLY NNE IN COOUR
CE
I'OEPOWN75 01W THE CONTRACTOR, ANSWER QUESTIONS RESOLVE Mr FROM THE, SERVICE PANEL. /0 A DISCONNECT SERVICE BOK LOCATED
CONFLICT 159UES AND SCHEDULE INSPECTION STE V975 BASED ONAJACET TO THE POST MOUNTED TOM CONTROL PANEL ELECTRICIAN
CONSTRUCTION PROCESS A PRI CONSTRUCTION MEETING WTI THE TO RUN TELEPHONE SEANCE MIRE TO PANEL FROM PHONE SERVICE BOX
r ENGINEER. SUPPLER. THE CONTRACTOR. ELECTRICIAN ANO TIE QUALIFIED TERMINATE IN PANEL WEN APPROPRIATE PHOS LNE CONNECTOR.
-
NSTAlER IS ESSENTIAL AND REQUIRED PRIOR ro NSTAUTICN OF THE
OMS COMPONENTS PRE CONSIA)C110N CONSIA.TATION INSPECTIONS AND 1 M SYSTEM QUALIFIED INSTALLER SHALL INSTALL ELECTRICAL DIRECT
STARTUP BY AL SERVICE SEPTIC AND/OR VALLEY PRE CAST, We IS BURT 1WIE5 FROM M CONTROL PANEL TO THE TREATMENT AND DOSING
E.E INCLUDED IN M SYSTEM COST. PUMP ASSEMBLIES 494CTM BOXES IN TIE RESPECTIVE RISERS OVER
M TREATMENT TAMIL INSTALL COLOR LVED WNES PEA
S OL
TMENTINSTALL
OLSNT
E REOUATICUS REQlNE THAT THE DESIGN ENONEM OF RECORD PANEL DIAGRAM. ALL CURES FOR PUMP AND OPER CN WM
PERFORM STE NSPECIKNS OF M PERMITTED SYSTEM MARRING COMQIT SEAL NEM FUSER SPLICE BOIL ELECTRIAN TO COORDINATE W/
CONSTRUCTION AND PPONOE'AS-BAON T` DOCUMENTATIOF THE SYSTEM NSTAUER. FOR RECIRCULATIONASSEMBffS INSTALLATION
INSTALLED SYSTEM TO THE THE COUNTY AFTER CONSTRUCTION IS CONSULTATION ALL SERVICE SEPTIC AND/Oft BY VALLEY PRECAST. INC.
COMPLETE WE RECOMMEND INSTALLED OWS: _ C SURVEYED TO OBTAINGUNEDATAS-BUILT NTFORYAC IMPON. NT$ BE ows I)= cnrf RIA
4
B.
CONTRACTOR SHOULD OtSCU= ISSUES REGARDING SPECIFICATIONS.
INSTALLATION
NTH THE WAND SW FAAC7�ER5 MECHANICAL
(AALLSAND
SEO E
SEPTIC AND/OR VALLEY PRE GST) AND/OR M ENGINEER
7.
OUR DESIGN AND RECOMMENDATIONSPROPOSED
SITE
ARE BASED UPON OUIRDEV LOPMENTO/
OF NS E105I ANO PROPOSED DTE C s NYO D4 THE IF DEVIR PM
PLANS AND TE CONDITIONS
ONDI SUPPLIEDAFI RE UT 8T OTHERS K DF.ELOPMET/r
ROWS OR SHE CONDI OR
ARE FANO ro E DIFFERENT FROM
CVALUAT b ASSEFED at NTHE PRO, IED SHOULD E NOTIFIED ro
EVALUATE ANr EFFECT ON M PROPOSED OK
IL
CONTRACTOR BAUD THEW ANT ER INS ON ONE ISSUED PERMIT
T
AND COOONIATE WM M ENGINEER ORNEDREGARDING CONSTRUCTION OF M
SYSTEM. FORUM IF YCU HAVE ANT QUESTION ENGIN CW NEED TT ADOITOUL
WFOIYA710N, PLEASE CULL M ENIGNER.
S
A OMM SHALL
YANTENAN T A?HEEMwE NTH A CERTIFIED SERVICE
PEAtEE 1 SNARE P MADE NTH IN VOE O AND nwflEO EVERY 3
'T.eRl iD InlIE[ Paeme MAINTENANCE OF
THE SYSTEMS
IS
PEVGRm
GROFEM 1ROlQORR DIZTPT—'F!N`-P WSPIRSAF,
FDiID CALCULATION
OI�ISLAR� QETRQEMF.ACB DTVPNWUT.-
PUMP �Z6 CALCULATION
From No Carty OWEL R*WMLon;
O :: na l0) _ I a PaPN XM
SEW/p"N/do, law nn)
MAXMat p Ilea (OC) � 0 • 1.5 (PaaVM9 fap ) - 90/IVY (CAVI)
4 tt b bout ARb arNat* ACU QTS
Drys bond an 2 PWAWI* D• bod NN tad S betroWna
Por cegt. too - 75 SEM/p/day
04 . 4.b7L1.5 .900 9d/dor
TOM PVaM D•Wr Flee M 900 god/do,
srlM Tent a
AI
RVmm�mWid -WWQ a TSW 2000 MIaN�'Nt btobnrlt dPNv taN m
AW%N tMw N* dH y N M. oIN al* ea g •Hlurt IMV b IN D -Bea
T'V,t TaIN Eben Haw Not bI —tight toR odrto-
OWW W Mom~ to foNOM Aum* oaulpmNt Nam VIA" PTI CoA.
A goloo er d etw*tl9Vtlr .0 Porfarmod bF BE A Penn IMo or
Nrwbd L* 7 drA aN a aMloo tnrdl .r r*awtN to EDM, a
AWNWAV W USDA Aol aleWMaYW. TM rI a lY erp epp— to IY a
MbAY ,V1 loom to at, do, loom. A hyd—oRW MdYMo i. b.uq
pnNmaa
to AWNar daWt, aN dot—Mo N• wooM9 tat, Wo
Nat aW Woom" rate W 0.3 9W./SF/d" . &ooVhK, W I— WV oipactW
to W b*Mo a mW. — .1 7 Nat Mm Wo o.Mm AI9fadr in tM
na W* PPw� d* flow. Ne •Ma Wo a 9tntl - oa. W Lood
HM WOWV p+L
TM voW.noo d*MWI bFwWPNa IaadVq tat* M 0.3 gd/SF./CRY W W*
natlw Venn 12-16 — PMN tM .urba* 9— N Mo bM— Th -
I, .,
obFafuYM l_Mg — oM 0.3 9d/SF.I., oN uaoo to .M• 1M
Pr MN IC d'M A.n-- Tho I7o— PYaVlda* W Wtomnttrt P.Arto
Carew DIM .IAN !oval and filo WwbtW WltftY of —too eMaont ut hul19
Blo .tanaerd C000— drpYo _g W Mto uto" tM drgl I—o tole.
gfflf����
*d sEaom to PPaa.r*o by on AN lYbe Frt)nWtt WIN OMat A Enol W* rplk taW oMurt or.r M nal6 7M teNLAd oMINrt oN fM proun* sora W Wrwll N* MIo at (nquWlt NtWwM tAnuyl dMdlq tr1pNMoW amt" dM W
W ofMrt N M baN into rl nadrd
ae9. owr N ePorapa iT N w d Taal.* WMund N. a ft' aHPII.
aMtI,ou oa otm t.N� W dxrwd nob utNVNl9 tM IaadH9 nt* W
N* near oao M ePPaaNWtMY 3000 SF arumMq No .tmaWa Y m
Z. WRitM reo*p and W mMenun Y o.PWvaWV e•t.Nn drfdM.
W Th
*W
cdobtN toed NrV9N of trMM• M 1500 LF.
No o..umo Nat N* Rola oR o MVt a 12 1—oadl 725 Not long ar
1R Harm Na 194 ANI long Tho .MWY and r•h•n Ilea m ft
aur
.W b* N P1* _.tmdl an.
art Yaa EaM IM, 0f ,.—..VI a
M' Plgll —t YM OM — La aamMW alW a W ntwq to
MAN an
NI \]P gad.oa�Pl IOYTNto- 0E-9lR-OMS-:
Z
Q
a
Y mi
W LLT
Lu
[If U)
U >-
U U)
Z
W
cm)
Z
Q
Lu pW
o O �
� U �
Lu z
U Y H
H
55 Lli
p W
Lu r
LL cf)
Z Z
W p
Y �
U W
w
Z
W p
2
]FTE: 02-1-11
.TOR ND. 120Ma
-,HE--I 1 CF 2
?RESSURE DOSED GEOFLOI DRIPLINE FIELD NOTES
THE DIMENSIONS AND NOTES SHOWN ON THE PLAN INDICATE MINIMUM
AREA, LENGTH, WIDTHS AND SEPARATION DISTANCES FOR THE DRIPLINE
LAYOUT. THE TOTAL LENGTH OF DRIPLINE LATERALS SHALL BE
INSTALLED IN A CLUSTERED ARRAY TO BE DETERMINED IN THE FIELD.
2. THE DRIPLINES SHALL BE INSTALLED IN NARROW TRENCHES EXCAVATED
RELATIVELY LEVEL FOLLOWING THE EXISTING GRADE CONTOURS. THE
DRIPLINE LATERALS WILL BE PLACED IN THE 8"-16" DEEP TRENCHES
OVER THE NATIVE SOIL AND BACKFILLED WITH THE NATIVE SOIL. THE
TRENCH BOTTOM AND SIDEWALLS SHALL BE SCARIFIED AND/OR
RACKED IF SMEARING OCCURS.
GENERAL NOTES r
EXISTING CONDITIONS ARE SCHEMATIC ONLY, BASED ON FIELD MEASUREMENTS
AND OBSERVATION. ACTUAL COMPONENT INSTALLATION LOCATIONS WILL BE FIELD
DETERMINED PER THE INTENT OF THE PLAN. THE PROPOSED OWS DESIGN IS BY
SOPRIS ENGINEERING, LLC.
OWS SYSTEM NOTES
1. ALL MATERIALS AND INSTALLATION SHALL CONFORM TO STATE AND COUNTY
INDIVIDUAL SEWAGE DISPOSAL SYSTEM ISDS REGULATIONS.
2. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO CONTACT UTILITY LOCATORS
AND UTILITY COMPANIES AS NEEDED FOR FIELD LOCATIONS OF UTILITIES PRIOR TO
CONSTRUCTION AND EXCAVATION.
3. INSTALL THE "WASTE FLOW PC DRIPLINE" PRESSURE COMPENSATING 3. ALL GRAVITY SEWER LINES TO BE 4" SDR -35, OR SCHEDULE 40 P.V.C. PIPE
DRIPLINES WITH EMITTERS ON 2' CENTERS. EQUAL PRESSURE UNLESS NOTED OTHERWISE. ALL GRAVITY SEWER LINES TO BE INSTALLED ON A
DISTRIBUTION OVER THE ENTIRE FIELD WILL BE MAINTAINED. 2% GRADE. LINES MAY BE STEPPED DOWN BETWEEN 2% RUNS. FITTINGS AT ALL
VERTICAL AND HORIZONTAL BENDS NOT TO EXCEED 45. USE CLASS 6 BEDDING.
4. DISPERSAL FIELD W/ PRESSURE DOSED CEO FLOW DRIPLINES. LAYOUT
OF GEOFLOW DISPERSAL ARRAYS, AND DISTRIBUTION PIPING TO BE 4. ALL PRESSURE LINES TO BE SCHEDULE 40 P.V.C. OR HDPE SDR -7 PIPE UNLESS
FIELD DETERMINED TO INSURE OPTIMAL PERFORMANCE, INSTALLATION NOTED OTHERWISE. PRESSURE LINES TO BE INSTALLED WITH A MINIMUM 2%
EFFICIENCY AND TO PRESERVE VEGETATION TO THE MAXIMUM EXTENT GRADE FOR DRAIN BACK. NO LOW POINTS OR DIPS ARE ACCEPTABLE ALONG
POSSIBLE. PRESSURE PIPE RUNS. AIR RELEASE MECHANISMS REQUIRED AT ALL HIGH POINTS.
FITTINGS AT ALL VERTICAL AND HORIZONTAL BENDS NOT TO EXCEED 45'.
5, INSTALL THE SPECIFIED LENGTH OF 1/2" GEOFLOW WASTE FLOW PC
DRIPLINE WITH DRIP EMITTERS ON 2' CENTERS. THE ASSUMED LENGTH
OF EACH DRIPLINE LATERAL SHALL BE APPROXIMATELY AS SHOWN ON
THE PLAN. THE DRIPLINE LATERALS SHALL BE INSTALLED IN AN ARRAY
OF NEAR PARALLEL LATERALS GENERALLY FOLLOWING THE CONTOURS
WITHIN OPEN AREAS OF THE FIELD SITE. LINES TO BE INSTALLED AT
M * DEPTH NOT TO EXCEED 16" IN NARROW TRENCHES TO AVOID
DISTURBANCE OF EXISTING VEGETATION TO THE PRACTICAL EXTENT
POSSIBLE. THE MINIMUM SEPARATION DISTANCE BETWEEN LATERALS IS
2 FEET HOWEVER THE SEPARATION DISTANCE MAY BE VARY BASED ON
VEGETATION, GRADES AND OTHER EXISTING CONDITIONS WITHIN THE
FIELD AREAS.
6. THE DRIPLINE LATERALS SHALL BE INSTALLED TO PROVIDE A MINIMUM
15" OFFSET OF THE FIRST AND LAST EMITTER FROM THE SUPPLY AND
RETURN MANIFOLDS RESPECTIVELY. THE 1" DIAMETER MANIFOLDS SHALL
BE INSTALLED AT CONTINUOUS SLOPE DOWN FROM THE MOST
UP -GRADIENT LATERAL TO THE DOSING TANK TO INSURE POSITIVE
DRAINBACK THROUGH THE SUPPLY AND RETURN MANIFOLDS. THE
RETURN MANIFOLD INVERT SHALL BE APPROXIMATELY 6" LOWER THAN
THE SUPPLY MANIFOLD. INSTALL AIR VACUUM BREAKERS AT THE
HIGHEST POINTS ON THE DISPERSAL FIELD (ON THE TERMINAL ENDS OF
THE MANIFOLD LINES).
7, THE DRIPLINES ARE INSTALLED FROM THE MANIFOLD WITH 1" PVC TEES,
COMPRESSION FITTING ADAPTERS AND COMPRESSION COUPLERS AS
NEEDED.
8. ALL INSTALLATION OF DRIPLINES AND DISTRIBUTION MANIFOLDS SHALL
BE IN CONFORMANCE WITH THE MANUFACTURES INSTALLATION
INSTRUCTIONS. (SEE ATTACHED MATERIAL).
9. THE DISPERSAL FIELD MUST BE GENERALLY LOCATED ON AN AS -BUILT
DRAWING AND POSSIBLY WITH SURFACE RISER/STAKES AND/OR BURIED
RE BAR AT KEY DIMENSION POINTS. THE FIELDS MUST BE PROTECTED
FROM VEHICULAR AND LIVESTOCK TRAFFIC.
10. ANY POTENTIAL SURFACE DRAINAGE SHALL BE ROUTED AWAY FROM
THE FIELD.
11. THE ENTIRE DISPERSAL FIELD SURFACE MUST BE RE VEGETATED
TESTING. INSPECTIONS_ AND CONSTRUCTION MANAGEMENT
I. ADDITIONAL GEOTECHNICAL EVALUATIONS AND INSPECTIONS BY THE
ENGINEER WILL BE PERFORMED AS A BASIS FOR THE FINAL DISPERSAL
FIELD DESIGN. ADDITIONAL INSPECTIONS AND RECOMMENDATIONS WILL BE
MADE BY THE ENGINEER DURING INITIAL STAGES OF CONSTRUCTION TO
VERIFY ASSUMPTIONS MADE FOR THE OWS DESIGN.
2. SOPRIS ENGINEERING HAS PERFORM SOIL PERCOLATION RATE TESTS IN
r m nn nn n..rn . nr • i.r ++ .r n.r.nrn•+., r. r. n rn nrrrn. n.m r .r
5. ALL GRAVITY AND PRESSURE LINE TO BE BEDDED AND BACKFILLED WITH SUITABLE
NATIVE SOIL OR CLASS -6 ROAD BASE IN TRENCHES WITH UNDISTURBED SUB
GRADE SOIL OR COMPACT SUB GRADE AS NEEDED. LOCATION OF BURIED PIPES TO
BE MARKED IN THE FIELD.
6. ALL PVC PIPE SHALL BE CUT WITH A PIPE CUTTER. SAWING PVC IS PROHIBITED TO
PREVENT ACCUMULATION OF SMALL FILINGS IN THE PRESSURE DOSED SYSTEMS.
ALL PVC TO BE SOLVENT WELDED.
7. INSTALL A TWO-WAY CLEAN OUT ON THE SERVICE LINES FROM ALL BUILDINGS.
ADDITIONAL CLEANOUT REQUIRE AT UPSTREAM GRADE BREAKS, AND AT A MINIMUM
100' DISTANCE ALONG ALL GRAVITY LINES.
8. THE SEPTIC TANKS SHALL BE WATERTIGHT AND INSTALLED LEVEL ON COMPACTED
EARTH. THE TANKS SHALL BE CERTIFIED AS WATERTIGHT BY THE MANUFACTURE.
MID SEAM TANKS SHALL BE TESTED FOR WATER TIGHTNESS AFTER PLACEMENT
AND PRIOR TO BACKFILL. CONTRACTOR TO INSTALL THE WATERTIGHT RISERS AS
NECESSARY TO BRING ALL REQUIRED ACCESS POINTS TO THE FINISHED SURFACE
GRADE. ALL RECIRCULATION AND DOSING TANKS SHALL HAVE ORENCO RISERS AS
NOTED ON PLANS.
9. A SANITARY BAFFLE TEES ARE REQUIRED ON ALL PRIMARY SEPTIC TANK INLETS
AND OUTLETS, (DO NOT INSTALL SANITARY BAFFLE TEES IN RECIRCULATION
TANKS). INSTALL ONLY INLET TEES ON DOSING TANKS. INSTALL ALL SANITARY
TEES PLUMB AND IN A POSITION TO ALLOW EASY INSPECTION AND MAINTENANCE
OF TANK FROM THE TANK RISERS.
10. FOR PUMP SYSTEMS: WE RECOMMEND THE INSTALLATION OF AN ORENCO BIO -TUBE
SCREEN VAULT FOR THE SPECIFIED PUMP ASSEMBLIES TO BE INSTALLED IN THE
TANK OR PUMP BASIN. THE FILTER SHOULD BE INSPECTED EVERY SIX MONTHS.
THE EFFLUENT FILTER SHALL BE MAINTAINED AND CLEANED WHEN THE TANK IS
PERIODICALLY PUMPED OR AS NECESSARY. INSTALL A SUITABLE EXTENSION ON
THE FILTER HANDLE IF NEEDED FOR EASY ACCESS IN RISER.
11. THE CONTRACTOR SHALL ENSURE THAT THE SEWER LINES, SEPTIC TANK AND
RISERS ARE WATERTIGHT. ALL PLUMBING FIXTURES AND OWS COMPONENTS SHALL
BE INSTALLED AND MAINTAINED TO AVOID SURFACE OR GROUNDWATER FROM
ENTERING THE SYSTEM AND TO PREVENT LEAKAGE FROM THE SYSTEM. IN-HOUSE
PLUMBING FIXTURES SHALL BE MAINTAINED TO PREVENT EXCESS WATER FROM
ENTERING THE SEPTIC SYSTEM.
12. THE INSTALLATION OF THE TREATMENT, DISTRIBUTION AND CONTROL COMPONENTS
WILL REQUIRE INCIDENTAL ASSEMBLY EQUIPMENT AND MATERIALS TO BE PROVIDED
BY VALLEY PRECAST.
13. AT THE OWNERS EXPENSE, A MANUFACTURES REPRESENTATIVE (ALL SERVICE
SEPTIC AND/OR VALLEY PRECAST, INC.), WILL PROVIDE TECHNICAL SUPPORT AND
INSTALLATION CONSULTATION TO THE CONTRACTORS, INSTALLERS AND ELECTRICIAN
ON-SITE DURING CONSTRUCTION. ALL SERVICE SEPTIC AND/OR VALLEY PRECAST
WILL INSTALL THE TREATMENT SYSTEM AND PERFORM INSPECTIONS.
L
f
rz
f
p
i
u
I. ADDITIONAL GEOTECHN, _.,L EVALUATIONS AND INSPECTIONS BY THE
ENGINEER WILL BE PERFORMED AS A BASIS FOR THE FINAL DISPERSAL
FIELD DESIGN. ADDITIONAL INSPECTIONS AND RECOMMENDATIONS WILL BE
MADE BY THE ENGINEER DURING INITIAL STAGES OF CONSTRUCTION TO
VERIFY ASSUMPTIONS MADE FOR THE OWS DESIGN.
2. SOPRIS ENGINEERING HAS PERFORM SOIL PERCOLATION RATE TESTS IN
THE PROPOSED AREA OF THE DISPERSAL FIELD TO DETERMINE THE
HYDRAULIC LOADING RATE OF THE SOIL 10" TO 20" BELOW THE SURFACE.
A SERIES OF CONTROLLED DOSED INFILTRATION TEST MAY BE PERFORMED
TO DETERMINE THE SOILS BEHAVIOR AND ACCEPTANCE OF TREATED
WASTEWATER AT A SPECIFIED RATE.
3. THE ACTUAL LAYOUT OF THE DISPERSAL FIELD AND THE ASSOCIATED
DRIPLINE LATERALS AND MANIFOLDS WILL BE DETERMINED IN THE FIELD
AND APPROVED BY THE ENGINEER.
4. PRIOR TO CONSTRUCTION OF THE PERMITTED SYSTEM THE ENGINEER
SHOULD BE CONTACTED BY THE PROJECT MANAGER/CONTRACTOR WELL IN
ADVANCE TO PROVIDE ADEQUATE TIME TO DISCUSS THE SYSTEM
COMPONENTS WITH THE CONTRACTOR, ANSWER QUESTIONS, RESOLVE ANY
CONFLICT ISSUES AND SCHEDULE INSPECTION SITE VISITS BASED ON
CONSTRUCTION PROGRESS. A PRE-OWS CONSTRUCTION MEETING WITH THE
ENGINEER, SUPPLIER, THE CONTRACTOR, ELECTRICIAN AND THE QUALIFIED
INSTALLER IS ESSENTIAL AND REQUIRED PRIOR TO INSTALLATION OF THE
OWS COMPONENTS. PRE CONSTRUCTION CONSULTATION INSPECTIONS AND
STARTUP BY ALL SERVICE SEPTIC AND/OR VALLEY PRE CAST, INC. IS
INCLUDED IN THE SYSTEM COST.
5.
REGULATIONS REQUIRE THAT THE DESIGN ENGINEERS OF RECORD
PERFORM SITE INSPECTIONS OF THE PERMITTED SYSTEM DURING
CONSTRUCTION AND PROVIDE "AS -BUILT" DOCUMENTATION OF THE
INSTALLED SYSTEM TO THE THE COUNTY AFTER CONSTRUCTION IS
COMPLETE. WE RECOMMEND THAT INSTALLED OWS COMPONENTS BE
SURVEYED TO OBTAIN REQUIRED AS -BUILT INFORMATION.
6.
CONTRACTOR SHOULD DISCUSS ISSUES REGARDING SPECIFICATIONS,
INSTALLATION AND OPERATION OF OWS MECHANICAL SYSTEMS AND
CONTROLS WITH THE MANUFACTURERS REPRESENTATIVE (ALL SERVICE
SEPTIC AND/OR VALLEY PRE CAST) AND/OR THE ENGINEER.
7.
OUR DESIGN AND RECOMMENDATIONS ARE BASED UPON OUR EVALUATION
OF THE EXISTING AND PROPOSED SITE CONDITIONS, THE DEVELOPMENT
PLANS AND INFORMATION SUPPLIED TO US BY OTHERS. IF DEVELOPMENT
PLANS OR SITE CONDITIONS ARE FOUND TO BE DIFFERENT FROM
CONDITIONS ASSUMED OR INDICATED, WE SHOULD BE NOTIFIED TO
EVALUATE ANY EFFECT ON THE PROPOSED OWS.
8.
CONTRACTOR SHOULD REVIEW ANY CONDITIONS ON THE ISSUED PERMIT
AND COORDINATE WITH THE ENGINEER REGARDING CONSTRUCTION OF THE
SYSTEM. IF YOU HAVE ANY QUESTION OR NEED ANY ADDITIONAL
INFORMATION, PLEASE CALL THE ENGINEER.
9.
A CONTRACTUAL MAINTENANCE AGREEMENT WITH A CERTIFIED SERVICE
PROVIDER SHALL BE MADE WITH THE OWNER AND RENEWED EVERY 3
YEARS TO INSURE PERIODIC MAINTENANCE OF THE SYSTEMS IS
PERFORMED.
Worksheel - Field Desien
uantity ofeffluent to be disposed perdav
900 gallons i
day
Hvdraulic loading rate
0.3 allons /.
.ft. / day
Determine total area required
3000 square ft.
Chooses acing between WASTEFLOW lines
2 ft.
Choosespacing between WASTEFLOW emitters
2 ft.
Total linear ft.
1501 1 zone
Total number of emitters
750 each
Select Wastetlow dripline
wastetlow PC 2 gph
dripline
Pressure at the beginning of the dri field
''-0 psi
Feet of Head at the beginning, oCthe dri field
46.2 ft.
What is the flow rate peremitterin h?
0.53 gallons per
hour
Total flow for the area ( hl
398 eallonsper
hour
Total flow for the area ( m)
4.63 ga Ions per
minute
Select Pine diameters for manifolds and submains
1 inch
Select Vortex Filter fitem no.)
Con ult factory
Maximum length of each WASTEFLOW line. For
Additional technical flow, pressure and flushing data
please refer to Geoflow's Design Manual and
WASTEFLOW hydraulics worksheet.
424
-
ft.
Dosin
Number of doses per day/zone:
Pump run time per dose/zone ('minutes):11.32
Pump run time per day/zone (hours):
Pump nm time per day/all zones fhoursl:
12
minutes
2.'_6 hoots ;day
1.1(,I hours
Dri line Volume
Tubing Inside diameter
0.55 inches
Total len nth of WASTEFLOW dri linei zone
150 R
Total Volume in dri line i zone
18.5 allons
GEOFLOW SUBSURFACE DISPERSAL:
PITIM RMF. rATrTTT.ATTnv
BY VALLEY PRECAST.
13. AT THE OWNERS EXPENSE, A MANUFACTURES R ESENTATIVE (ALL SERVICE
SEPTIC AND/OR VALLEY PRECAST, INC.), WILL PROVIDE TECHNICAL SUPPORT ANI
INSTALLATION CONSULTATION TO THE CONTRACTORS, INSTALLERS AND ELECTRICI
ON—SITE DURING CONSTRUCTION. ALL SERVICE SEPTIC AND/OR VALLEY PRECAST
WILL INSTALL THE TREATMENT SYSTEM AND PERFORM INSPECTIONS.
ELECTRICAL NOTES (TYP ALL DUPLEX PUMP ASSEIMLIES)
1. A CONTROL PANEL SHALL BE INSTALLED BY A ELECTRICIOAN IN
COORDINATION WITH THE ELECTRICIAN. WE RECOMMEND 230 VOLT
ELECTRIC SERVICE BE PROVIDED TO THE PUMP AND AERATION BLOWER
THE POWER SUPPLY FOR THE PUMP. AIR UNIT AND CONTROLS SHALL
CONSIST OF (2) 20 AMP DOUBLE POLE CIRCUITS FOR THE PUMPS AND
(1) 10 AMP SINGLE POLE CIRCUIT FOR CONTROLS. PANEL TO BE
INSTALLED IN LINE OF SITE WITH TREATMENT TANK.
2. THE CONTRACTOR SHALL INSTALL ELECTRICAL SUPPLY WIRE IN CONDUIT
FROM THE SERVICE PANEL TO A DISCONNECT SERVICE BOX LOCATED
AJACET TO THE POST MOUNTED TO THE CONTROL PANEL. ELECTRICIAN
TO RUN TELEPHONE SERVICE WIRE TO PANEL FROM PHONE SERVICE BOX.
TERMINATE IN PANEL WITH APPROPRIATE PHONE LINE CONNECTOR.
3. THE SYSTEM QUALIFIED INSTALLER SHALL INSTALL ELECTRICAL DIRECT
BURY WIRES FROM THE CONTROL PANEL TO THE TREATMENT AND DOSING
PUMP ASSEMBLIES JUNCTION BOXES IN THE RESPECTIVE RISERS OVER
THE TREATMENT TANK. INSTALL COLOR CODED WIRES PER CONTROL
PANEL DIAGRAM. INSTALL ALL WIRES FOR PUMP AND CONTROLS WITH
CONDUIT SEAL NEAR RISER SPLICE BOX. ELECTRIAN TO COORDINATE W/
SYSTEM INSTALLER. FOR RECIRCULATION ASSEMBLIES. INSTALLATION
CONSULTATION ALL SERVICE SEPTIC AND/OR BY VALLEY PRECAST, INC.
OWS DESIGN CRITERIA
From the County OWTS. Regulation;
Average daily flow (0) _ # of people x gal/person/day (avg. flow)
Max. Design flow (Qd) = Q x 1.5 (peaking factor) = gal/day (design)
4 bedroom house with separate ADU OWTS
Design based on 2 persons per bedroom with total 5 bedrooms
Per capita flow = 75 gal/person/day
Qd = 4x2x75x1.5 =900 gal/day
Total Peak Design Flow is 900 gal/day
Septic Tank and treatment tank:
Exisitng septic tank capacity is 1500 gal
Recommend Instolingl a 1500-2000 MicroFast treatment dosing tank in
series below the driveway in line with the existing effluent line to 1st D—Box
Treatment Tank shall have cast inplace watertight riser adapters.
Details for MircoFast to follow: Assume equipment from Valley Pre Cast.
Sub Surface Conditions and Testina:
A Subsurface soil investigation was performed by SE. A profile hole was
excavated to 7' deep and a shallow trench was excavated to obtain soil
samples for USDA soil classification. The soil at 12" deep appears to be a
blocky clay loam to silty clay loam. A hydrometer Analysis is being
performed to further cla and determine the loading rate. We assume
that the loading rate i 0.3 als/SF/day. . Groundwater levels are expected
to be below a minimum et from the existing surface grades in the
area of the proposed drip field. o evidence of groudwater was encountered
in the profile pit.
Soil Dispersal S,�tem Design: 7j 5 L�P_ I r �1
`{i Ct L 5V I CI C,,/ )
The assumed design hydraulic loading rate is 0.3 gal/S.F./day for the
native soils 12-18 inches below the surface grades on the hillside. The
conservative hydraulic loading rate of 0.3 gal/S.F./day was used to size the
preliminary drip field system. The system provides for intermittent pressure
dosing treated effluent, in shallow driplines, across the field. The dispersal
area is sized based on the calculated quantity of treated effluent utilizing
the standard Geoflow dripline sizing criteria utilizing the design loading rate.
The dripline dispersal system is proceeded by an ATU (Micro Fast)
secondary treatment unit that will treat the septic tank effluent prior to
discharge to the field. The treated effluent will be pressure dosed in small
quantities across the field at frequent intervals through individual dripline
laterals. The small amount of treated effluent will infiltrate into the natural
soils over an average 12" diameter radius around the individual dripline
emitters. The area required for dispersal field utilizing the loading rate for
the native soils is approximately 3000 S.F. assuming the standard 2' on
center emitter spacing and the minimum 2" separation between dripline
laterals. The calculated total length of dripline is 1500 L.F.
We assume that the field will consist of 12 laterals each 125 feet long or
16 laterals each 194 feet long. The supply and return line manifold pipes
will be in the some trnch on the east side. Each pair of laterals will be
looped on the west side with each loop connected with a tee fitting to an
air bleed manifold.