ONSITE WASTEWATER TREATMENT SYSTEM (OWTS)
CONSTRUCTION PERMIT
76 Service Center Rd- Aspen, CO - 81611
Phone: 970.920.5070 Fax: 970.920.5374
Permit #: 0036.2013.powt Parcel ID #:
2645-234-10-001
Permit Issued: ®NEW CDU ❑REPAIR ❑REMODEL/ADDITION ❑TANK ONLY ❑FIELD ONLY ❑AMENDMENT
Owner(s): Bruce T Halle
Property Address:
Legal Description:
390 Popish Rd
Lot 8 Wildcat Ranch
Size of Lot: 593.717
Size of Building: 2841
Acres
Sq. Ft.
Detached Accessory Unit:
Size of Accessory Unit:
❑YES ®NO
The system is designed for: A Barn with 3 employees and a toilet, hand sink, and kitchen sink.
Designed By:
Phone #:
Fax #:
All Service Septic Project #: _
970-618-5033 Mailing Address:
303-216-2796 Email Address:
Perc Rate: 0.5 LTAR
Minimum Tank Capacity:
C1051 Dated
PO Box 2844 Glenwood S
Sq. Ft.
Nugust 27, 2013
CO 81602
Profile Hole Depth: 8 ft (pit 1) Depth to Groundwater or Bedrock: 6.5 ft (pit 1)
141 gallons Minimum Absorption Area: 222 ft2 (30% reduction)
Permit Conditions:
This OWTS Construction Permit is approved on the condition of compliance with the engineer design as submitted with the application and the specifications
cited above. Changes must be approved by this Department and the engineer prior to construction.
This permit is for a new OWTS system for a reconstructed barn with 0 bedrooms and 3 employees.
Groundwater was not observed in the second profile pit (pit 2), closest to the proposed soil treatment area at the time of the
site inspection. The system shall consist of sewage flowing via gravity to a 1000 -gallon, two-compartment septic tank with an
effluent filter installed in the second compartment. Effluent will gravity flow from the tank to a distribution box and then two
gravelless chamber trenches. Each trench will have 12 Quick -4 chambers for a total of 24 chambers. The soil treatment area
shall be a minimum of 50 feet to the irrigation ditches. Floor drains in the barn shall not be connected to the OWT system but
connected to a dry well.
This Permit must be kept on-site during installation. The engineer must do a final inspection of the installation and submit an "as -built" letter to this
Department within 30 days of the final inspection, unless a longer period of time has been agreed upon, in writing. This Department must also be called for
the final inspection with a minimum of 48 hours notice.
Minimum horizontal distances between components of the system and physical features shall conform to the requirements of the Pitkin County OWTS
Regulation.
This Permit is conditioned upon the property owner(s) providing for regular inspection, cleaning, and maintenance of the system by qualified personnel, in
accordance with the manufacturer's recommendations and the requirements of the Pitkin County OWTS Regulation. Issuance of this OWTS Construction
Permit does not constitute a guarantee, warranty, or representation by the Department that the system will operate properly or will not fail. Issuance of this
permit does not imply compliance with Pitkin County building and/or land use regulations, nor guarantee issuance of building and/or land use permits.
THIS PERMIT IS EXPRESSLY CONDITIONED UPON COMPLIANCE WITH ALL REQUIREMENTS OF THE PITKIN
COUNTY OWTS REGULATION, INCLUDING BUT NOT LIMITED TO THOSE CONDITIONS SPECIFIED ABOVE.
Plans and specifications for the proposed OWTS have been reviewed and are considered satisfactory. Permission is hereby
given to the property owner(s) to perform the work indicated in accordance with the Pitkin County OWTS Regulation. This
Permit will expire 1 year from the date of issuance unless construction on the system has commenced. An "as -built" drawing
must be submitted and approved by EH before final approval of the system will be issued.
Issued By: �� - uS? Date: 10/02/13 Expires: in/n?/2m4
Installer:a. J n. e. License #:
�,�-
Reactivation Authorized by:
Final Approval? By: Date: }
KJ Gtv� 1 L?
New Expiration Date: E] �P
0 1, 1 ir.. ", 1,
PO Box 2844
Glenwood Springs, CO 81642
0nr , 974.618.5033
R(� Fax 303-216.2796
October 26, 2013
Clay Lowery
cploweryAme.com
Onsite Wastewater Treatment System (OWTS) Installation Observations
Meadowbarn
350 Popish Road
Pitkin County, Colorado
OWTS Construction Permit Number 0036.2013.powt
Clay,
Project No. C 1051
W_
ALL SERVICE septic, LLC observed the installation of the onsite wastewater treatment system
(OWTS) on October 9, 2013 for the subject property. Savage Excavation installed the system.
The installation included a new 1000 -gallon, two-compartment Valley Precast concrete septic tank
with an effluent filter on the outlet tee. The inlet line and tee were not installed at the time of the
inspection; however, a photo of the tee installation was provided by the installer. Effluent gravity
flows to a distribution box, accessible from grade, and then to two gravelless chamber trenches. Each
trench consists of 12 `Quick 4' Infiltrator® chambers fora total of 24 chambers and 237 square feet
of infiltrative area. 6 -feet of undisturbed soil was present between each trench.
The OWTS was generally installed according to specifications. This observation is not a guarantee
of workmanship and/or parts and materials. ALL SERVICE septic, LLC should be notified if
changes are made to the OWTS in the future. Any additional OWTS construction must be according
to the county regulations.
LIMITS:
Observations are limited to components that are visible at the time of the inspection. The installer
must have documented and demonstrated knowledge of the requirements and regulations of the
county in which they are working. The quality of the installation is dependent of the expertise of the
installer, soil type, and weather conditions.
Please call with questions.
Sincerely,
ALL SERVICE septic, LLC
Carla Ostberg, MPH, REHS
Reviewed By:
Richard H.
H
1000 -gallon, two-compartment Valley Precast septic tank
Inlet tee
Effluent filter
Distribution box
Absorption trenches
b-teet of undisturbed soil between trenches / Good bedding around pipes
A
N --ank
0 10' 20'
Scale: 1" = 20'-0"
1
DESIGN '1111111111F
BARN
BATHROOM & KITCHEN SINK
ESTIMATED AVERAGE DAILY FLOW = 113 GALLONS
DESIGN FLOW = Q = 1.5 x 113 = 170 GALLONS
TANK:
170 x 30 HOUR RETENTION TIME = 212 GALLONS
USE 1000 -GALLON, TWO-COMPARTMENT TANK
ABSORPTION AREA:
LONG TERM ACCEPTANCE RATE (LTAR) = 0.5 GAL/ SQ FT
CALCULATED ABSORPTION AREA = Q/LTAR = 340 SF
30% REDUCTION, TRENCHES
TOTAL AREA REQUIRED = 238 SF
24'QUICK 4' CHAMBERS
TWO TRENCHES, EACH WITH 12 'QUICK 4' CHAMBERS
DITCH
P-1
F-1
O
OBSERVATION PORT
50' MINIMUM
DITCH S TBACK 'QUICK4' CHAMBER a fn
TRENCHES. 12 CHAMBERS
P-2 PER TRENCH = 237 SF
DISTRIBUTION \
BOX TO GRADE
1000 -GALLON,
TWO-COMPARTMENT
CONCRETE SEPTIC TANK
EFFLUENT FILTER —
4" SDR -35 SEWER LINE --
WITH CLEANOUT
(SLOPE 2% TO TANK)
4" SDR -35 SEWER
LINE TO D -BOX _
(SLOPE 1% ) Propos
(`^/, Propos
n RECORD DRAWING
BARN
DRIVE
Optional UM
Edas of Drive
Smo thiy Connect Proposed des
with Ezisting Grades
M iMatntn Historical Drain. e
P.O. Box 2844
Meadowbam Ranch
Date: 10/07113
n
L Glenwood Springs, Colorado 81602
350 Popish Road
Designed By: CBO
record
Se Phone 970.618.5033
Pitkin County, Colorado
Fax 303.216.2796
SENVICf
Checked By: RHP
Project Number. C1051
Drawn By: ANG
Sheet 1 of 1
f
oo36. Zo13, u°owT
ONSITE WASTEWATER TREATMENT SYSTEM (OWTS)
CONSTRUCTION PERMIT APPLICATION
76 Service Center Rd • Aspen, CO •81611
00 Phone: 970.920.5070 Fax: 970V0.5374
Parcel ID# (available from the Pitkin County Assessor's Office
970.920.5160 or at www oitkim ssessor om1:
e ?_7 / 1 j o COO/ v
`7 / CO
Purpose of Permit: O NEW ❑ REPAIR DUE TO FAILURE Q REMODEL/ADDITION iJ TANK ONLY ❑ FIELD ONLY
Cost of System Repair or RemodellAddition (approximate):
Cell Phone: 110 -7 f r —070ci
!£,
Property Address . •
/'`
Lot: cs} Block: FiilrV, Subdivision:,
roperty Owner(s)': 90146e. ,-- Email Address:
rwner's Mailing Address: P- ny City, State, Zip;
lame Phone: Business Phone: (?70
Contact information must be provided for the owner signing this application.
Primary Contact Person/Applicant (if not owner): _)j rq f
ttf tilt .
Company:
i` a IL rtf ,,v f i i f%t 7 111^ IC
Contact/Applicant Mailing Address.,,_
City, State, Zip:
Cell Phone: 110 -7 f r —070ci
!£,
Business Phone: �. ry r Cir
Fax Number: 7c, 7 s Gj
��
Email Address: {
Building Permit# (if applicable): f —40
Lot Size (in acres): — 7� 7
Size of Building (square feet):Number of Potential Bedrooms:
2!)` r r
Detached Accessory Unit?❑YES ❑ NO Size of Accessory Unit (square feet):
Number of Potential Bedrooms In or Fixture List for the AccessoryUnit:
Water Source:
❑ PRIVATE WELL [3 SURFACE WATER El SPRING tai COMMUNITYJPUBLIC WATER SYSTEM
Name of Community/Public Water System (if applicable): �„ q g
Engineering Firm: Job Number. Phone Number. -7 t t ax Number: .L
(%ft Ir C.01 %✓
Mailing Address:, r) City. State, Zip:, ItCz3
. %X 17
PLEASE READ BEFORE SIGNING:
I certify that the above information is complete and accurate and that I have provided comto
and accurate information In of the documents
included In my application package. I acknowledge that EHINR may revoke any permit I am issued if my application is found to contain any
inaccurate, false, or misleading information. I understand that no construction may be undertaken on an OWTS until an OWTS Construction Permit is
issued.
Owner Signature (Required): Date:
Applicant Signature: Date:
FOR OFRCE VeE OINL
Received y EN/HR Sir Fee & Recei t Date:
C1198.00 z/�18 2- 201
AA is ,',,,-- ntivrs Cnns2 orms W 15 construction permit app ication.xis Updatad: SO 7 OS
L7:��
Ho
PO Box 2844
Glenwood Springs, CO 81602
Ph 970.618.5033
Fax 303.216-2796
August 27, 2013
Clay Lowery
c 1p oweEyAme.com
Subsurface Investigation and Onsite Wastewater Treatment System Design
Meadowbarn
350 Popish Road
Pitkin County, Colorado
Clay,
Project No. C1051
ALL SERVICE septic, LLC performed a subsurface investigation and an onsite wastewater treatment
system (OWTS) design for the subject residence. The property is located outside of Aspen, in an area
where OWTSs and wells are necessary.
SITE CONDITIONS
A barn with no plumbing presently exists. There is a desire to rebuild the barn and add a bathroom to
the structure. A ditch runs to the north of the barn. A minimum 50 -foot setback will need to be
maintained to the proposed absorption area.
SUBSURFACE
The subsurface was investigated by digging one 8 -foot and one 7.5 -foot profile pit and taking a soil
sample from Pit 2 approximately 3 -feet below grade. A gradation analysis and hydrometer analysis was
run by HP Geotech and results are detailed in a report dated August 19, Job No 113 064P.
The materials encountered in the Pit 2 consisted of dark brown, dense, moist loam to 4.0 -feet, underlain
by brown, dense, moist loam to a maximum depth explored of 7.5 -feet. No bedrock or groundwater was
encountered in Pit 2. A pipe was placed in the Pit 2 to monitor for groundwater. Groundwater was
encountered in Pit 1 at 6.5 -feet. The gradation performed by HP Geotech shows the soil consists of
5% gravel, 35% sand, 48% silt and 12% clay. The USDA soil type is classified as Loam. A long
term acceptance rate (LTAR) of 0.5 gal/sq. ft will be used to design the OWTS.
August 9, 2013 (ditch running)
Page 2
Profile Pit 1 (P-1) 8 -feet (groundwater estimated at 6.5 -feet) Approx. 30 -feet from ditch.
Profile Pit 2 (P-2) 7.5 -feet (no groundwater encountered) Greater than 50 -feet from ditch.
DESIGN SPECIFICATIONS
The OWTS design is based on fixtures to be installed in a barn for use by 3 people daily. The
fixtures include a toilet, lavatory, and kitchen sink. An average daily wastewater flow of 113 GPD
will be used. The installation must include a 1000 -gallon, two-compartment septic tank with an
effluent filter on the outlet tee. Effluent will gravity flow to a distribution box, accessible from grade,
and then to two gravelless chamber trenches. Each trench will have 12 `Quick 4' chambers for a total
of 24 chambers and 238 square feet. There must be at least 6 -feet of undisturbed soil between each
trench.
The component manufacturers are typical of applications used by contractors and engineers in this
area. Alternatives may be considered or recommended by contacting our office. Construction must
be according to Pitkin County Onsite Wastewater Treatment System Regulations, the OWTS
Construction Permit provided by Pitkin County Environmental Health Department, and this design.
0 •
Page 3
REVEGETATION REQUIREMENTS
An adequate layer of good quality topsoil capable of supporting revegetation shall be placed over the
entire disturbed are of the OWTS installation. A mixture of native grass seed that has good soil
stabilizing characteristics (but without taproots), provides a maximum transpiration rate, and competes
well with successional species. No trees or shrubs, or any vegetation requiring regular irritation shall be
plated over the area. Until vegetation is reestablished, erosion and sediment control measures shall be
implemented and maintained on site. The owner of the OWTS shall be responsible for maintaining
proper vegetation cover.
OPERATION INFORMATION AND MAINTENANCE
The property owner shall be responsible for the operation and maintenance of each OWTS servicing the
property. The property owner is responsible for maintaining service contracts for manufactured units,
alternating absorption systems, and any other components needing maintenance.
Geo -fabrics or plastics should not be used over the absorption area. No heavy equipment, machinery, or
materials should be placed on backfilled absorption area. Livestock should not graze on the absorption
area. Plumbing fixtures should be checked to ensure that no additional water is being discharged to
OWTS. For example, a running toilet or leaky faucet can discharge hundreds of gallons of water a day
and harm an absorption area.
The homeowner should pump the septic tank every two years, or as needed gauged by measurement of
solids in the tank. Garbage disposal use should be minimized, and non -biodegradable materials should
not be placed into the OWTS. Grease should not be placed in household drains. Loading from a water
softener should not be discharged into the OWTS. No hazardous wastes should be directed into the
OWTS. Mechanical room drains should not discharge into the OWTS. The OWTS is engineered for
domestic waste only.
ADDITIONAL CONSTRUCTION NOTES
If design includes a pump, air release valves and weep holes should be installed to allow pump lines
to drain to minimize risk of freezing. Excavation equipment must not drive in excavation of the
absorption area due to the potential to compact soil. Extensions should be placed on all septic tank
components to allow access to them from existing grade.
INSTALLATION OBSERVATIONS
ALL SERVICE septic, LLC must view the OWTS during construction. The OWTS observation
should be performed before backfill, after placement of OWTS components. Septic tanks, distribution
devices, pumps, dosing siphons, and other plumbing, as applicable, must also be observed. ALL
SERVICE septic, LLC should be notified 48 hours in advance to observe the installation.
`.wr *4001
LIMITS:
Page 4
The design is based on information submitted. If soil conditions encountered are different from
conditions described in report, ALL SERVICE septic, LLC should be notified. All OWTS
construction must be according to the county regulations. Requirements not specified in this report
must follow applicable county regulations. The installer should have documented and demonstrated
knowledge of the requirements and regulations of the county in which they are working.
Please call with questions.
Sincerely,
ALL SERVICE septic, LLC
e6t'tt (�J_ os-�&As
Carla Ostberg, MPH, REHS
Reviewed
Y
Richard H
•
0 ch
HEPWORTH-PAWIAK
August 19, 2013
CBO Inc.
Attn: Carla Ostberg
33 Four Wheel Drive Road
Carbondale, Colorado 81623
carla.ostberts(cr�gmail.com
0
Hepworth-Pawlak Geotechnical, Inc.
5020 County Road 154
Glenwood Springs, Colorado 81601
Phone: 970-945.7985
Fax: 970-945-8454
Email: hpgeo @ hpgeotech.com
Job No. 113 064P
Subject: Laboratory Test Results, 350 Popish Road, Pitkin County, Colorado
Dear Mrs. Ostberg:
As requested, Hepworth-Pawlak Geotechnical, Inc. performed gradation analysis on a
sample delivered to our laboratory by you. The services were performed in accordance with
our agreement for professional engineering services to you, dated March 20, 2013.
Results of the gradation analysis performed on the sample are presented on Figure 1. The
USDA Soil Texture Classification is Loam.
If you have any questions or need further assistance, please call our office.
Sincerely,
HEPWORTH — PAWLAK GEOTECHNICAL, INC.
Louis E. Eller
LEE/ksw
attachment Figure 1 — USDA Soil Texture Gradation Test Results
Parker 303-841-7119 • Colorado Springs 719-633-5562 - Silverthorne 970-468-1989
N
0' 20' 40'
Scale: 1" = 40'-0"
2
W2.0
o
I �
17-1
DRIVE
I
l 1
- - .
320 POPISH RD
DRIVEWAY
rc>
m3
3�
Zo
n SITE PLAN
IP'0. Box 2844 Meadowbarn Ranch Date: 08/27/13
` Glenwood Springs, Colorado 81602 350 Popish Road , A' • O
SEflYICE SCpt�G Phone 970.618.5033 Pitkin County, Colorado Designed By: CBO VV
Fax 303.216.2796 Checked By: RHP
Project Number: C1051 Drawn By: ANG Sheet 1 of 3
N -==k— DESIGN
BARN
BATHROOM &KITCHEN SINK
0' 10' 20' ESTIMATED AVERAGE DAILY FLOW = 113 GALLONS
Scale: 1" = 20'-0" DESIGN FLOW = Q = 1.5 x 113 = 170 GALLONS
TANK:
170 x 30 HOUR RETENTION TIME = 212 GALLONS
USE 1000 -GALLON, TWO-COMPARTMENT TANK
ABSORPTION AREA:
LONG TERM ACCEPTANCE RATE (LTAR) = 0.5 GAL/ SQ FT
CALCULATED ABSORPTION AREA = Q/LTAR = 340 SF
30% REDUCTION, TRENCHES
TOTAL AREA REQUIRED = 238 SF
24'QUICK 4' CHAMBERS
TWO TRENCHES, EACH WITH 12'QUICK 4' CHAMBERS
1000 -GALLON,
TWO-COMPARTMENT
CONCRETE SEPTIC TANK WITH
EFFLUENT FILTER
4" SDR -35 SEWER LINE
WITH CLEANOUT
(SLOPE 20/ TO TANK) l
2 PROPOSED OWTS
BARN
DRIVE
Optional Culvr
Edqe of Drive
Smo thly Connect Proposed G des
."t Exlsting Grades
M intoinin Historical Drain. e
I P.O. Box 2844 Meadowbarn Ranch Date: 08/27/13
L Glenwood Springs, Colorado 81602 350 Popish Road Designed By: CBO W2.0
SERVICE S�Pt� Phone 970.618.5033 Pitkin County, Colorado
Fax 303.216.2796 Checked By: RHP
Project Number: C1051 Drawn By: ANG Sheet 2 of 3
�P1
` \
50' MINIMUM
s�
DITCH SETBACK
OBSERVATION PORT
o,
o�
0
e
'QUICK -4' CHAMBER
�n
TRENCHES. 12 CHAMBERS
P-2/_
PER TRENCH = 237 SF
DISTRIBUTION
\
BOX TO GRADE
8'
4" SDR -35 SEWER
LINE TO D -BOX
1
(SLOPE 194,. MIN.
propos
n
2.
1000 -GALLON,
TWO-COMPARTMENT
CONCRETE SEPTIC TANK WITH
EFFLUENT FILTER
4" SDR -35 SEWER LINE
WITH CLEANOUT
(SLOPE 20/ TO TANK) l
2 PROPOSED OWTS
BARN
DRIVE
Optional Culvr
Edqe of Drive
Smo thly Connect Proposed G des
."t Exlsting Grades
M intoinin Historical Drain. e
I P.O. Box 2844 Meadowbarn Ranch Date: 08/27/13
L Glenwood Springs, Colorado 81602 350 Popish Road Designed By: CBO W2.0
SERVICE S�Pt� Phone 970.618.5033 Pitkin County, Colorado
Fax 303.216.2796 Checked By: RHP
Project Number: C1051 Drawn By: ANG Sheet 2 of 3
DRAIN FIELD CROSS SECTION
- TYP.
INFILTRATOR(R) QUICK4(TM) CUT SHEET
DO NOT GLUE
FINISHED
GRADE
4' PVC
EFFLUENT LINE - 4"
52" OBERVATION
SEWER LINE -
35 P.V.C.
4fi" PIPE
40 P.V.C.
4" PVC
(EFFECTIVE LENG )
WIRE MAY BE INSTALLED TO
OBERVATION
34"
PIPE
1
3.5' max
UNDISTURBED'
SOIL
L
2'min
I6^
6' min
I
LIMIT OF
EXCAVATION
LINES TO ENTER
GRAVELLESS'QUICK-4'
AND EXIT IN TOP
SCARIFY SURFACE
CHAMBER (4'x 3')
PORT OF CHAMBER
END PLATE
PLAN VIEW - TYP.
12 CHAMBERS PER TRENCH
CHAMBER DETAILS
raT
n CLEANOUT DETAIL
Or To scut
VELLESS'QUICK-4'
MBER (4'x 3')
FLUENT PIPE
N SEPTIC TANK
RIBUTION
.S PLACED IN
PORT OF
CHAMBER END
PLATES
BOX AND COVER BROUGHT TO GRADE
CONCRETE LID
FINSHED GRADE
0000
INLET
OUTLETS
DISTRIBUTION BOX BAFFLE
�SLOX DETAIL
Of TD iilm
Septic Tank with the Addition of an Effluent Filter - 1000 Gallon, 2 -Comp.
/CoMrek IRsen\
ape pan
Asay From a
7o Oft" to come
1' from ""of
tank
Inlet Tee— I
ORENCO BRAND NAME
NOT ENFORCED
n TANK DETAIL
P.O. Box 2844 Meadowbarn Ranch Date: 08/27/13
} Glenwood Springs, Colorado 81602 350 Popish Road W3.0 A ,�. O
L 5CPf1C Phone 970.618.5033 Pitkin County, Colorado Designed By: CBO VV
SfflYICE Fax 303.216.2796 Checked By: RHP
Project Number: C1051 Drawn By: ANG Sheet 3 of 3
Niter Cartridge Handk
(field cut to desired lie lit)
Tank Adapter (cast or bolted)
Vet Orifice
Effluent D'mcho g,
kloduldng Dechorge Orifi
Vault Inlet Porti
Carlrk*
at Filter
SLIP-ON PVC CAP
DO NOT GLUE
FINISHED
GRADE
EFFLUENT LINE - 4"
SCHEDULE 40 OR 4" SDR
SEWER LINE -
35 P.V.C.
4"SCHEDULE
40 P.V.C.
INSULATED COPPER TRACER
WIRE MAY BE INSTALLED TO
LOCATE LINE IN FUTURE
n CLEANOUT DETAIL
Or To scut
VELLESS'QUICK-4'
MBER (4'x 3')
FLUENT PIPE
N SEPTIC TANK
RIBUTION
.S PLACED IN
PORT OF
CHAMBER END
PLATES
BOX AND COVER BROUGHT TO GRADE
CONCRETE LID
FINSHED GRADE
0000
INLET
OUTLETS
DISTRIBUTION BOX BAFFLE
�SLOX DETAIL
Of TD iilm
Septic Tank with the Addition of an Effluent Filter - 1000 Gallon, 2 -Comp.
/CoMrek IRsen\
ape pan
Asay From a
7o Oft" to come
1' from ""of
tank
Inlet Tee— I
ORENCO BRAND NAME
NOT ENFORCED
n TANK DETAIL
P.O. Box 2844 Meadowbarn Ranch Date: 08/27/13
} Glenwood Springs, Colorado 81602 350 Popish Road W3.0 A ,�. O
L 5CPf1C Phone 970.618.5033 Pitkin County, Colorado Designed By: CBO VV
SfflYICE Fax 303.216.2796 Checked By: RHP
Project Number: C1051 Drawn By: ANG Sheet 3 of 3
Niter Cartridge Handk
(field cut to desired lie lit)
Tank Adapter (cast or bolted)
Vet Orifice
Effluent D'mcho g,
kloduldng Dechorge Orifi
Vault Inlet Porti
Carlrk*
at Filter
qA o N
OF ^ss s>kayo �--�
0� �q SIM �g0
ry. --
Jam., ate zmma�o _ °° ow_zm
_ z �„11
5 -�wWB
mw ° Mo >.o 1. o omw W.
Q U W Q
: 4
J y
06
r
A U m
.Id 'f I[ZOO LL ZOO weg —PeaW a11eHlIaW W web —P -N all°H lNleg m°PeaWrsl�aladlYP9daOlpwgr
Alk
91 WOO".1N30H'MMM-OOY210'103139tl"Il1A SSO'WMONS z
�'r ' s'.�3a'�O�r R«<+ sssrsea a<m xva s<sesrero«anoxa HONVN IVOOIIM`S OY3J.SSWOH n
ios�s oo •w�waas aaoMn�o ASAIS SNOWONOO
HA9NLLSIX3 w ® �'
�o� �s •annanv asr,a <m� e. O
Lo8tl61�ZZ onauv` uo nli OOtlMOlOOSStlWMONS ry S
.�°��� +>3 Non;in3e azva on tea, 'DNI `9NR133N19N3 AL1NIlOD H91H ON� iaa.ur+�atl coma atlas ^
i�.
gwo
W r;
a s I ff
O a
Y Q
�n o
2
oe
z<
0,
z
4
O k� }_
IL
;
gt
Z 0' F` es `ag k
� IL rF
LO Q 417
i F awo r W g ae ag $
i Q O84 .s � b
2
U°
w0
U)
F
Zw1 Y
U) I y
-
W L vA
O
Z
Ln
LL
A
O
iW
Ea
0 s
to
W W
L n
t
1 \)
$44
aA=•�
3t�s°
�g�ygs
ei�6a
Y�a4�
W 1 L D C A T It A N C H
To: Pitkin County Environmental Health Department
Fr: Mike Thomas — PWS 0149-185
Date: August 29, 2013
This is to verify that lot 8, 350 Popish Rd., Wildcat Ranch, Snowmass Village has adequate water to
supply the barn remodel currently under review by the Pitkin County Health Department.
The barn is serviced by the Wildcat Ranch water system, a public water system. Wildcat's public water
system id is 0149-185.
WILDCAT RANCH ASSOCIATION
0875 WILDCAT WAY • P.O. BOX 274
S N O W M A S S, COLORADO 8 1 6 5 4
TEL 970.923.2841 • FAX 970.923.2157
Mea�Dwbc�-►�_
The Halle residence at Wildcat Ranch is located at 350 Popish Road. The
ranch entrance is approximately 4 miles from the Aspen Airport and 9 miles
from the city of Aspen.
From The Airport: Make a left onto HWY 82. Shortly after passing Brush Creek Rd, make a left on Lake
Wildcat Rd at mile marker #33. The road is unmarked but has a very large rock at its entrance.
From I-70: Exit at HWY 82, Glenwood Springs. Make a right off the exit, right on 6th St., and right on
Grand Ave. (HWY 82). Continue for 32.6 miles. Make a right onto Lake Wildcat Rd. at the large rock.
Gate Code is #4600 \ `
3 Miles
From Hwy 82
Popish road continues around the
corner and Halle Driveway starts Popish Rd.
here at the stop sign _
New Barn
Green House
Old
�OGuest House
Truck
��Turnaround
Main House
Lake Wildcat Rd.
N
S
dow Barn (WCNBP)
E
Project is here
Hwy
82
Wildcat Ranch
Halle Residence Map
Aspen Airport
w
P p
Popish makes a sharp right turn near the entrance to the Halle's property. The driveway is approximately
1 mile long. A barn is located on the left, a pond on the right. The guesthouse is on the left 1/2 mile from
the entrance to the property. The main house is at the top of the driveway. 0 0 N OT u s E G P S.