MEMORANDUM
Board of County Commissioners
Suzanne Konchan, County Manager
Lee Cassin and Betsey Kipp, Environmental Health
W/J Expanded Filing 2, Septic System Information
August 19,1996
Purpose: This memo provides a summary of technical information and the conclusions of
CH2MHill's two reports. A Registered Professional Engineer (RPE) conducted these studies,
and this memo summarizes the engineer's analysis. It first summarizes CH2MHi11's
examination of the adequacy of existing septic systems on the W/J Ranch. It also describes
alternatives CH2MHill discussed for resolving problems with existing septic systems. Finally, it
describes CH2MHill's analysis of the ability of platted vacant lots to accommodate septic
systems in Filings 2 and 3.
Discussion: Details, conclusions, and recommendations are the result of the RPE's analysis,
physical examination and in -field measurements of existing systems, and review of existing
permits.
I. * ADEQUACY OF EXISTING SEPTIC SYSTEMS:
A. Present condition and performance of existing septic systems and system sizes
• Septic systems in Filing 1 are presently sized for the existing 2-bedroom homes. (There is
a formula for the area required per bedroom. The actual area was determined by in-
field measurements of the systems. Dividing the actual area by the required area per
bedroom tells how many bedrooms the systems were designed for.)
• Septic systems in Filing 2 are adequately sized for 3 of the 6 existing homes. The other
three homes have septic systems that are too small to comply with present regulations.
Five of the systems are on a different lot.
• Septic systems in Filing 3 are adequately sized for some of the existing homes, but too
small for others.
B. Expansion potential to size allowed by approvals
• CH2MHill notes, "the majority of the lots in both filings [1 and 3] would have difficulty
with installation of a septic system designed to serve a four bedroom house under the
best circumstances."
• In Filing 2, there are 6 developed lots. Three do not have room for any septic system.
Two have room for expanded systems by removing driving and parking areas. One may
have room to expand if parking areas and water lines are removed.
Page 2
• CH2MHill notes that "if the County wishes to allow the addition of bedrooms, it should
evaluate servicing these subdivisions in an area' wide wastewater treatment plant rather
than by individual systems."
C. Location of systems within lot boundaries that the system serves
Setback Requirements (These are the required separation between septic systems and
water lines, property lines, buildings, wells, irrigation lines, etc. )
• In Filing 1, according to the CH2MHill report, only 1 of the 27 houses has a septic system
that meets the setback requirements in the County regulations
• In Filing 2, only 1 home has a septic system on its own lot, and it does not meet setback
requirements.
• In Filing 3, 6 of the septic systems do not meet setback requirements; 1 does.
D. Large number of septic system repairs at W/J
• There has been an unusually high number of repairs of septic systems at W/J. We do
not know why so many systems needed repair permits, and why some systems had to
be repaired twice within a few years.
E. Lack of permits and RPE designs for Filing 1
• There is no record of any septic permits for the new septic systems in Filing 1, either in
our files, or in the records of installers, engineers, or consultants. Permits were required
for this work. Our department also has logs of all the permits issued, and a permit for
Filing 1 of W/J does not appear on the log.
• There are two septic systems in Filing 1 that the regulations required to be designed by
a Registered Professional Engineer (RPE), but there is no indication of an RPE design.
II. * Alternatives/Actions to resolve systems on adjacent lots
• If there is a package treatment plant, all homes and lots can continue to exist as is, and
homes can be expanded
• Lot line adjustments and/ or elimination of lots to allow other lots to expand would
allow the remaining lots to be developed and the existing houses to expand. Any
relocation or expansion of a septic system requires compliance with the present code.
III. * Ability of platted vacant lots to accommodate septic systems within Filings 2 and 3
• There are 9 vacant lots in Filing 2. Seven (7) could accommodate homes and individual
septic systems by relocating existing septic systems that encroach onto these lots;
relocating roads and parking areas; and relocating water lines. The other 2 lots may be
too constrained if relocated septic systems cannot fit on their "own" lots Lot expansions
may be an available option.
•
Printed on Recycled Paper
Page 3
e There are 3 vacant lots in Filing 3. Two can accommodate individual septic systems. The
third has two existing septic systems from other houses located on it, and it may not be
possible to relocate one of these.
IV. * Recommendation: CH2MHi11's report states that the State is "unlikely to approve a
system which is not adequately sized to serve all three filings." The Division has told us the
same thing, that they "would be unlikely to approve any site applications at W/J until there is a
master plan for the whole area." CH2MHi11 recommended a package treatment plant and
recommended that any common system be maintained and operated by the Aspen
Consolidated Sanitation District (ACSD).
CH2MHill stated, "It is also recommended that if the county wishes to allow the addition of
bedrooms, it should evaluate servicing these subdivisions in an areawide wastewater treatment
plant rather than by individual systems."
The CH2MHi11 report also states that "approval by the State of the construction of a new
wastewater treatment plant is not assured. Approval is much more likely if all the filings are
addressed."
"It is recommended that the installation of an extended aeration plant be pursued. It is also
recommended that consolidation of the wastewater treatment for the three filings be further
pursued and researched."
Printed on Recycled Paper
TO:
FROM:
RE:
DATE:
MEMORANDUM
Board of County Commissioners
Suzanne Konchan, County Manager
Lee Cassin and Betsey Kipp, Environmental Health
W/J Expanded Filing 2, Septic System Information
August 19,1996
Purpose: This memo provides a summary of technical information and the conclusions of
CH2MHill's two reports. A Registered Professional Engineer (RPE) conducted these studies,
and this memo summarizes the engineer's analysis. It first summarizes CH2MHil1's
examination of the adequacy of existing septic systems on the W/J Ranch. It also describes
alternatives CH2MHi11 discussed for resolving problems with existing septic systems. Finally, it
describes CH2MHil1's analysis of the ability of platted vacant lots to accommodate septic
systems in Filings 2 and 3.
Discussion: Details, conclusions, and recommendations are the result of the RPE's analysis,
physical examination and in -field measurements of existing systems, and review of existing
permits.
I. * ADEQUACY OF EXISTING SEPTIC SYSTEMS:
A. Present condition and performance of existing septic systems and system sizes
• Septic systems in Filing 1 are presently sized for the existing 2-bedroom homes. (There is
a formula for the area required per bedroom. The actual area was determined by in-
field measurements of the systems. Dividing the actual area by the required area per
bedroom tells how many bedrooms the systems were designed for.)
• Septic systems in Filing 2 are adequately sized for 3 of the 6 existing homes. The other
three homes have septic systems that are too small to comply with present regulations.
Five of the systems are on a different lot.
• Septic systems in Filing 3 are adequately sized for some of the existing homes, but too
small for others.
•
B. Expansion potential to size allowed by approvals
• CH2MHill notes, "the majority of the lots in both filings [1 and 3] would have difficulty
with installation of a septic system designed to serve a four bedroom house under the
best circumstances."
• In Filing 2, there are 6 developed lots. Three do not have room for any septic system.
Two have room for expanded systems by removing driving and parking areas. One may
have room to expand if parking areas and water lines are removed.
Page 2
• CH2MHill notes that "if the County wishes to allow the addition of bedrooms, it should
evaluate servicing these subdivisions in an area wide wastewater treatment plant rather
than by individual systems."
C. Location of systems within lot boundaries that the system serves
Setback Requirements (These are the required separation between septic systems and
water lines, property lines, buildings, wells, irrigation lines, etc. )
• In Filing 1, according to the CH2MHil1 report, only 1 of the 27 houses has a septic system
that meets the setback requirements in the County regulations
• In Filing 2, only 1 home has a septic system on its own lot, and it does not meet setback
requirements.
• In Filing 3, 6 of the septic systems do not meet setback requirements; 1 does.
D. Large number of septic system repairs at W/J
• There has been an unusually high number of repairs of septic systems at W/J. We do
not know why so many systems needed repair permits, and why some systems had to
be repaired twice within a few years.
E. Lack of permits and RPE designs for Filing 1
• There is no record of any septic permits for the new septic systems in Filing 1, either in
our files, or in the records of installers, engineers, or consultants. Permits were required
for this work. Our department also has logs of all the permits issued, and a permit for
Filing 1 of W/J does not appear on the log.
• There are two septic systems in Filing 1 that the regulations required to be designed by
a Registered Professional Engineer (RPE), but there is no indication of an RPE design.
II. * Alternatives/Actions to resolve systems on adjacent lots
• If there is a package treatment plant, all homes and lots can continue to exist as is, and
homes can be expanded
• Lot line adjustments and/ or elimination of lots to allow other lots to expand would
allow the remaining lots to be developed and the existing houses to expand. Any
relocation or expansion of a septic system requires compliance with the present code.
III. * Ability of platted vacant lots to accommodate septic systems within Filings 2 and 3
• There are 9 vacant lots in Filing 2. Seven (7) could accommodate homes and individual
septic systems by relocating existing septic systems that encroach onto these lots;
relocating roads and parking areas; and relocating water lines. The other 2 lots may be
too constrained if relocated septic systems cannot fit on their "own" lots Lot expansions
may be an available option.
Printed on Recycled Paper
Page 3
• There are 3 vacant lots in Filing 3. Two can accommodate individual septic systems. The
third has two existing septic systems from other houses located on it, and it may not be
possible to relocate one of these.
IV. * Recommendation: CH2MHill's report states that the State is "unlikely to approve a
system which is not adequately sized to serve all three filings." The Division has told us the
same thing, that they "would be unlikely to approve any site applications at W/J until there is a
master plan for the whole area." CH2MHi11 recommended a package treatment plant and
recommended that any common system be maintained and operated by the Aspen
Consolidated Sanitation District (ACSD).
CH2MHi11 stated, "It is also recommended that if the county wishes to allow the addition of
bedrooms, it should evaluate servicing these subdivisions in an areawide wastewater treatment
plant rather than by individual systems."
The CH2MHi11 report also states that "approval by the State of the construction of a new
wastewater treatment plant is not assured. Approval is much more likely if all the filings are
addressed."
"It is recommended that the installation of an extended aeration plant be pursued. It is also
recommended that consolidation of the wastewater treatment for the three filings be further
pursued and researched."
Printed on Recycled Paper
MEMORANDUM
TO: Board of County Commissioners
Suzanne Konchan, County Manager
FROM: Lee Cassin and Betsey Kipp, Environmental Health
RE: W/J Expanded Filing 2, Septic System Information
DATE: August 19,1996
Purpose: This memo provides a summary of technical information and the conclusions of
CH2MHi11's two reports. A Registered Professional Engineer (RPE) conducted these studies,
and this memo summarizes the engineer's analysis. It first summarizes CH2MHi11's
examination of the adequacy of existing septic systems on the W/J Ranch. It also describes
alternatives CH2MHi11 discussed for resolving problems with existing septic systems. Finally, it
describes CH2MHill's analysis of the ability of platted vacant lots to accommodate septic
systems in Filings 2 and 3.
Discussion: Details, conclusions, and recommendations are the result of the RPE's analysis,
physical examination and in -field measurements of existing systems, and review of existing
permits.
I. * ADEQUACY OF EXISTING SEPTIC SYSTEMS:
A. Present condition and performance of existing septic systems and system sizes
• Septic systems in Filing 1 are presently sized for the existing 2-bedroom homes. (There is
a formula for the area required per bedroom. The actual area was determined by in-
field measurements of the systems. Dividing the actual area by the required area per
bedroom tells how many bedrooms the systems were designed for.)
• Septic systems in Filing 2 are adequately sized for 3 of the 6 existing homes. The other
three homes have septic systems that are too small to comply with present regulations.
Five of the systems are on a different lot.
• Septic systems in Filing 3 are adequately sized for some of the existing homes, but too
small for others.
B. Expansion potential to size allowed by approvals
• CH2MHil1 notes, "the majority of the lots in both filings [1 and 3] would have difficulty
with installation of a septic system designed to serve a four bedroom house under the
best circumstances."
• In Filing 2, there are 6 developed lots. Three do not have room for any septic system.
Two have room for expanded systems by removing driving and parking areas. One may
have room to expand if parking areas and water lines are removed.
Page 2
• CH2MHi11 notes that "if the County wishes to allow the addition of bedrooms, it should
evaluate servicing these subdivisions in an area wide wastewater treatment plant rather
than by individual systems."
C. Location of systems within lot boundaries that the system serves
Setback Requirements (These are the required separation between septic systems and
water lines, property lines, buildings, wells, irrigation lines, etc. )
• In Filing 1, according to the CH2MHill report, only 1 of the 27 houses has a septic system
that meets the setback requirements in the County regulations
• In Filing 2, only 1 home has a septic system on its own lot, and it does not meet setback
requirements.
• In Filing 3, 6 of the septic systems do not meet setback requirements; 1 does.
D. Large number of septic system repairs at W/J
• There has been an unusually high number of repairs of septic systems at W/J. We do
not know why so many systems needed repair permits, and why some systems had to
be repaired twice within a few years.
E. Lack of permits and RPE designs for Filing 1
• There is no record of any septic permits for the new septic systems in Filing 1, either in
our files, or in the records of installers, engineers, or consultants. Permits were required
for this work. Our department also has logs of all the permits issued, and a permit for
Filing 1 of W/J does not appear on the log.
• There are two septic systems in Filing 1 that the regulations required to be designed by
a Registered Professional Engineer (RPE), but there is no indication of an RPE design.
II. * Alternatives/Actions to resolve systems on adjacent lots
• If there is a package treatment plant, all homes and lots can continue to exist as is, and
homes can be expanded
• Lot line adjustments and/or elimination of lots to allow other lots to expand would
allow the remaining lots to be developed and the existing houses to expand. Any
relocation or expansion of a septic system requires compliance with the present code.
III. * Ability of platted vacant lots to accommodate septic systems within Filings 2 and 3
• There are 9 vacant lots in Filing 2. Seven (7) could accommodate homes and individual
septic systems by relocating existing septic systems that encroach onto these lots;
relocating roads and parking areas; and relocating water lines. The other 2 lots may be
too constrained if relocated septic systems cannot fit on their "own" lots. Lot expansions
may be an available option.
Printed on Recycled Paper
Page 3
• There are 3 vacant lots in Filing 3. Two can accommodate individual septic systems The
third has two existing septic systems from other houses located on it, and it may not be
possible to relocate one of these.
IV. * Recommendation: CH2MHill's report states that the State is "unlikely to approve a
system which is not adequately sized to serve all three filings." The Division has told us the
same thing, that they "would be unlikely to approve any site applications at W/J until there is a
master plan for the whole area." CH2MHill recommended a package treatment plant and
recommended that any common system be maintained and operated by the Aspen
Consolidated Sanitation District (ACSD).
CH2MHi11 stated, "It is also recommended that if the county wishes to allow the addition of
bedrooms, it should evaluate servicing these subdivisions in an areawide wastewater treatment
plant rather than by individual systems."
The CH2MHi11 report also states that "approval by the State of the construction of a new
wastewater treatment plant is not assured. Approval is much more likely if all the filings are
addressed."
"It is recommended that the installation of an extended aeration plant be pursued. It is also
recommended that consolidation of the wastewater treatment for the three filings be further
pursued and researched."
•
Printed on Recycled Paper
MEMORANDUM
TO: Board of County Commissioners
FROM: Betsey Kipp, Environmental Health Dept.
DATE: May 13, 1996
RE: Letter to W/J Homeowners
Attached is a copy of the letter that was mailed to all
homeowners at the W/J Ranch.
May 13, 1996
Dear W/J Homeowners:
ASPEN • PITKIN
ENVIRONMENTAL HEALTH DEPARTMENT
This letter is to let you know our department's process for
reviewing and approving building permits for any ,remodels,
additions, or basements. The size of your home and the number of
bedrooms allowed is a function of the land area available on your
lot. We will need to confirm and be provided with the following
information
1. Percolation report for your lot
2. Site plan showing surveyed property lines and the
location of your house on the lot
3. Floor plans of existing rooms and proposed
rooms
4. Verification of the size and components of the individual
sewage disposal system which services that dwelling
5. Location of water supply lines.
Unfortunately, there is.a lack of documentation and permits or
as -built drawings (especially in Filing #1). With information
that we do have, it appears that many homes do not have their
leach fields on their own lot, or share leach fields with other
dwellings. Many property lines also appear to encroach on the
setback requirement from a leach field. This means that, for many
homeowners, there is not enough room on their lot to'increase the
sewage disposal system as required. In addition, until land is
available for these expansions, building permits cannot be.
signed.
If your sewage disposal system reaches its absorption capacity, •
does not function properly, and is on another lot, it is possible
that there may not be adequate room on the your lot to•install
the replacement system. When this department learns that a system
is no longer working,' we are required to issue a notice of.
violation (NOV) andset a date for its repair. As the homeowner,
your responsibility will be to fill out the application with fee,
and provide us with the information as noted above.
•
•
130 SOUTH GALENA STREET • AsPFN, COLORADO 81611 . PHONE 303.920.5070 • FAx 303.920.5197
Printed on recyiled paper
It is important to remember that field verification will be
necessary by a member of this department when sewage disposal
system components must be exposed due to a lack of documentation.
This will be required for repairs or expansions for most lots.
We anticipate that there will be many questions as your plans
develop. The staff at the Environmental Health Department is
qualified to answer those questions and to design individual
sewage disposal systems/repairs should that be necessary. We look
forward to working with each homeowner.