MEMORANDUM
TO: Patrick Keelty
Keelty Construction
204 Park Ave, 1K
Basalt, CO 18621
(970) 927-6472; patrick@keeltyconstruction.com
FROM: Terry Bendetti, SGM
Thru: Dean Gordon, SGM
DATE: 3/17/2020
RE: Duckworth Residence OWTS
As requested, I reviewed the capacity for the constructed Onsite Wastewater Treatment
System (OWTS) for the residence located at 1000 South Starwood Drive, Pitkin County,
Colorado, the Duckworth Residence, and have determined the following.
HISTORY
Review of the OWTS capacity was prompted by the change in the number of bedrooms
available in the residence. During the Certificate of Occupancy review, the Building
Department determined a room that had previously been considered a study met the
requirements for a sleeping room. As such, Pitkin County Environmental Health
Department (PEHD) requested that a letter from the Engineer of Record be submitted to
PEHD stating the constructed OWTS would meet requirements for a 7 bedroom
residence.
Review of PEHD permit documents for permit No. 05078 reveal the following.
1. The original OWTS was designed to treat wastewater generated from a 6
bedroom home. However, due to lot restraints the system was designed as two
systems, the West System and the East System.
2. Plumbing for the house was designed and installed in a manner to collect and
proportionally discharge wastewater into the appropriate System to ensure that
overloading of either System did not occur.
Review of SGM’s records indicate the following:
1. System 1 was designed for 4 bedrooms and System 2 was designed for 2
bedrooms.
GLENWOOD SPRINGS 118 West Sixth St, Suite 200 | Glenwood Springs, CO 81601 | 970.945.1004
Page | 2
2. The design flow rate was increased from 75 gpd per occupant to 100 gpd per
occupant due to the livable space for the residence being over 6,000 square feet.
3. System 1 was designed for an average daily waste flow of 800 gpd and the
regulations at the time of design required a loading factor of 1.5 be applied to the
average daily waste flow, yielding a daily design flow of 1200 gallons.
4. System 2 was designed for an average daily waste flow of 400 gpd and the
regulations at the time of design required a loading factor of 1.5 be applied to the
average daily waste flow, yielding a daily design flow of 600 gpd.
5. An unlined sand filter was designed for each System and the long term
acceptance rate (LTAR) for an unlined sand filter at the time of design was
0.95gal./sq.ft./day. The thickness of the sand filter in each System is 2 feet.
6. The minimum soil treatment area (STA) for System 1 was calculated to be 1264
sq. ft. and 632 sq. ft. for System 2.
7. The septic tank for System 1 is 2000 gallons and 1500 gallons for System 2.
Both tanks have two-compartments with an Orenco Systems, Inc. Biotube pump
vault in the second compartment.
8. The recommended dosing pump for each System was an OSI Model PF3005 HH
pump.
9. An automatic distribution valve (ADV) was placed between the effluent pump in
the Biotube pump vault and STA for each system. The ADV installed for System
1 was an Orenco 6404 and for System 2 an Orenco 6403.
10. The discharge piping from the effluent pump to the ADV was 1.5 inch schedule
40 PVC.
11. The piping from the ADV to the STA was 1 inch diameter schedule 40 PVC pipe
with solvent welded joints.
12. The distribution system is a pressurized distribution system.
OWTS CAPACITY ASSESSMENT FOR A 7 BEDROOM SINGLE FAMILY RESIDENCE
USING PEHD REGULATION 43
I have concluded that under the 2012 design requirements the constructed OWTS cannot
handle 7 bedrooms.
However, using the information conveyed to me about the additional bedroom for the
residence, I have conducted a capacity analysis for a 7 bedroom single-family residence
for the subject property based on PEHD 2018 Regulation 43 requirements.
The following conditions for the analysis were used.
1. The single family residence has 7 bedrooms or the capacity for 14 occupants.
2. Waste generated from the additional bedroom, the 7th bedroom, is conveyed to
and treated in System 1. Therefore, System 1 treats wastewater for five
bedrooms having 2 occupants per bedroom, or a total of 10 occupants.
3. The design flow rate per occupant of 100 gpd per the 2012 design was
maintained due to the living area being greater than 6,000 sq. ft.
4. The STA is an unlined sand filter using secondary sand media having a LTAR of
0.8 gal/sq. ft/day, per sub-section 43.11.3.b.2 of PEHD Regulation 43. The
secondary sand media is based on the fact that sand available in the Pitkin
County area cannot meet the preferred sand media requirements.
5. No changes are applied to System 2, so it was not included in the analysis.
GLENWOOD SPRINGS 118 West Sixth St, Suite 200 | Glenwood Springs, CO 81601 | 970.945.1004
Page | 3
Based on the above conditions and in accordance with Table 6-1, sub-section 43.6 of
PEHD Regulation 43 the design flow rate for System 1 would be 1,000 gpd, as shown in
the following table.
No.
Bedrooms
No.
Occupants/Bedroom
No.
Occupants
Wastewater
Flow/Occupant
(gpd)
Design
Flow (gpd)
5 2 10 100 1000
Based on sub-section 43.10.c.4 and the LTAR for an unlined sand filter using secondary
sand, the size of the STA would need to be 1,250 sq. ft., (1000 gpd)/(0.8 gal/sq. ft./day).
Based on Table 9-1 of sub-section 43.9.B the septic tank size for 5 bedrooms would
need a minimum capacity of 1,500 gallons; 4 bedrooms at a capacity of 1,250 gallons
plus 1 bedroom at a capacity of 250 gallons.
SUMMARY
In accordance with SGM’s letter dated June 7, 2019 the system was constructed per the
design documents. Therefore, System 1 was constructed for 4 bedrooms, 8 occupants
or a total of 800 gpd with a STA having 1,264 square feet. The STA is an unlined sand
filter having a thickness of 2 feet. The distribution system is a pressurized system using
1-inch diameter schedule 40 PVC piping having a 3/16-inch diameter orifice drilled at
intervals of 3-feet. The spacing between distribution laterals is 3-feet, with the outer
lateral being 1.5-feet from the sidewall of the bed. Effluent from the laterals drain into
the bed between pump cycles to prevent freezing.
The additional bedroom to the residence is connected to system 1, which increases the
total bedroom count connected to System 1 from 4 bedrooms to 5, 10 occupants or a
total of 1,000 gpd. Comparison of the required septic tank capacity and STA square
footage for System 1 calculated using requirements from PEHD 2018 Regulation 43
compared to the as constructed septic tank capacity and STA square footage is shown
in the following table.
Septic Tank Size (gal) STA (ft2)
As Constructed 2,000 1,264
2018 PEHD Reg 43 Requirements 1,500 1,250
Review of the constructed pressure distribution system per the design drawings show
the system complies with subsections 43.10.E.3, 43.11.C.2 and 43.11.C.3 of PEHD
Regulation 43.
GLENWOOD SPRINGS 118 West Sixth St, Suite 200 | Glenwood Springs, CO 81601 | 970.945.1004
Page | 4
CONCLUSION
The as constructed System 1 OWTS meets the requirements of PEHD’s Regulation 43
for treating 5 bedrooms.
A copy of the installation acceptance letter dated June 7, 2019, a copy of the
stamped/signed OWTS design drawings and a copy of the pump selection for System 1
is included with this Memo.
Respectfully,
Terry Bendetti, PE
www.sgm-inc.com
GLENWOOD SPRINGS 118 West Sixth St, Suite 200 | Glenwood Springs, CO 81601 | 970.945.1004
June 7, 2019
Mr. David deL’Arbre via email: david@keeltyconstruction.com
Keelty Construction Inc.
Basalt, CO 81621
RE: Duckworth Residence, Lot R60, Starwood Subdivision
OWTS Installation
Dear David:
This is to document that I have inspected or supervised inspection of the above referenced OWTS and
found it to be in compliance with the approved plans and specifications. I understand the OWTS is in
operation presently and is functioning as designed.
Sincerely,
Dean Gordon
SGM
June 7, 2019
s =
� "<BU/LO/NC ENVELOPE
NEW 4" C900 DR 14 PVC ® CLEANOUT
I SEWER LINES 70 TANK \ �"
MIN. 2X SLOPE
S ® i
0
o zo w e0
(Of FUT i
GRAPHIC SCALE
1/Inen - 40 :r.
PROPERTY LINE t I ® :•I I
1 I I
1 I
4S
I
SEPAL ENVELOPE &_/�1!
I
PROPERTY SETBACK UNE 1"' SYS I ®o DUCKWOR7H RESIOENCE - 3< _ r
CLFANOUT
CLEANOUT
-GEOTHERMAL WELL (lYP) I I
�BUXD1NG ENVELOPE y I I
a I
i
PROPERTY UNf
`\
\V_25' GEOTHERMAL li I I I , SETBACK LIN�o NEW 4" C900 DR 14
SEWER LINES 70 I I NEW C900 DR
\ \ ®a TANK M/N. 2X SLOPE 14 UNES 712
®a TANK
SLOPE
/ \ CLEANOUI eo.. _ _ _ _ _ _ _ _ _ _ _
a
�\ SEMICK LINE
SYSTEM 2
I
� Y
g SGM Duckworth Residence OWTS p R Dob
By I
V 118 West SiAh Sheet, Suim 200
Gbnwood Springs, eo 81601 m Pitkin County, Colorado
970.945.1004 www.gminc.co
ENVELOPE R
7Y SETBACK UNE —
Property Ioft
m" M au
Site Plan ote: 10.24.12
C: PE: DG a o
n BY
N
N
0
NEW 2000 Cr1L. 2 COMPARTMENT
SEP77: TANK, TOP OF TANK 70
BE 5' BELOW RAISHED GRADE
SEE DETAIL FOR /NSTALLAAON
1.5 /NCH PVC SCH. 40
FROM DISCHARGE ASSEMBLY
70 ADV VALVE
AOV MODEL 6404 & AIR
RELIEF VALVE IN 24• PVC RISER
SWEN HIGH POINT
S££ DETAIL FOR INSTALLA77ON
141INCH SCH 40 PVC LINES
FROM V 77J ABSORPZ RELD
AMN/FOLLL4
MAN/FOLDS 70 BE
1 INCH SCH. 40 PVC
R£LD LA7ERALS 70 HE
1 INCH SCH. 40 PVC
I I G6 .1-- "4-s 4-s t 4s
I L
(D
Al G7
•y�4 INCH C900 DR 14
SEWER LINE FROM HOUSE
I i
G8
1 BUILDING ENVELOPE
96,
25' CE07HERAML
SEMCK LINE
� FLUSH/NC ASSEMBLY (7YP) G9
GEOTHERMAL WELL (7YP)
%G17
1 20 M/LL PVC LINER 70 BE
1 INSTALLED ON EAST & NOR7H
SIDES OF RELD
\\ 9Q G26
Duckworth Residence OWTS
Pitkin County, Colorado
►�4
IM
System 1
Design Layout
G1�
r+
rmMEMNON
MIMMMMMIMENNEN
■mmool
m�MMMME1
6 No. 2005521.001
own by: da
ik: 1024.12
C: PE: DG O! 6
un BM
0
0
N
x
Top
Vie w
Sectio)
Vie w
20" Clear Access II
�•{ .�.-_, /(Big Hole Lid & Riser)
Cqj
L
14ON A6RAR SEPAASMXN✓
FABRIC OR APPROVED EQUAL
—{ 1.00,
N4nW SOIL -
1 INCH PW LAMM (1YP) -i
AM 20 MILL PVC LINER
ACCORDING fit PLANS
Digging Specs
Invert
Dimensions
Net Capacity
15' Long x 8' Wide
56, below inlet invert
Inlet
56'
Outlet
73"
Length
162"
I Width
78'
I Height
92'
lnlet Side
1,559 gollons
Out/et Side
505 yol/ons
Total
2,064 gollons
Net We' ht Tom`
MsebA9TMC-1227spec
Lid Tank Total /nNudhrg C-f6f406hrnre//Nnf
5,420 lbs 15,530 lbs 21.150 lbs eonnsctont
4000 psi concrete
• Delivered complete with internal piping
1.5 FT EDGE --{ OF I FINLSHED GR"
FIELD
1 FT. ANA .7FT, AM
AMnW 8ICA6IIL I,- O0:w OW mp) 1 INCHES OF GRAVEL
ABOVE LATERALS
S4ND R/LT£R SEC17ON SYSTEM 1
xoT TO Scae
I. ABSORP71ON REEDS 70 8E A SWD
RL7ER /N ACCORDANCE WRN RI7X/N COUNTY
AND SOM REGULATIONS AND SPEORC4nONS
2. FIELD TO FOLLOW RNISHED GRADE
SURFACE IO ALLOW FOR OR4#94GE AS
SHOWN OW PLANS
.I EFFLUENT LINE MW PUMP 70 AOV 70
BE 1.5' PVC SCH 40. EFFLUENT CAVES FORM
AOV TO FIELD 70 BE I' PVC SCH 40.
4. LA7ERAL LINES 70 8E 1' PVC SCH. 40.
3/18 DRILL HOLES TO BE LOCATED EVERY 3'
AT 771E I2.-00 POSMOV AND 3/16' DRILL
HOLES AT 7NE &'O0 POS/I/OV 1' FROM 77IE
START AND END OF 7HE LATERAL. ORIRCE
SHIELDS A/OOEZ j OS 100 70 BE INSTALLED
OVER ALL UPWARD DRILL HOLES
5. FLLLSN/NC ASWkSLIES TO BE INSTALLED
AT THE END OF EACH LAIMC SEE DETAIL
DES// -A/ J/ //d1RXy
CHAMBERED DESIGN CRI7ER64
DESI&V FLOW - 1200 GPO
PERCOLA7XW R47E - 74 MPI
AREA® 12000PD/.95G4t,/SF/D4Y = 1264
6AND RLIER SPE07rATION5
NUMBER OF ZONES - 4
NUMBER OF LATERALS - 11
LEN07H OF LATERALS - JO FT.
DIMM70AIS 36 FT X 36 FT 7'
4-
70TAL AREA = 1296 5F
PIMP,
0
a
\ vi
3`— N4'S 4 's4"S 4^S —N4S —ii4'5 4'S VS — 1 4 S —H4"S —N4'S —{
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
I
G24 BUILDING ENVELOPE*
GEOTHERI AL WELL (IYP) /
/ ADV MODEL 6403 & AIR
RELIEF' VALVE IN 24- PVC RISER,
/ SYSTEM HIGH Po/NT.
25' CEOTHER414L SEE DETAIL FOR INSTALLATION
SE7340K LINE
(3) 1.5 INCH SCH. 40 PVC LINES
FROM ADV 70 ABSORPTION R7ELD
20 MILL PVC LINER 7O HE LATERAL ONES TO BE MANIFOLDS�-F--
INSTALLED ON EAST & NORTH 1.5 INCH PVC SCH. 40
SIDES OF FIELD AS SHOWN ®-�
tM FM FM
18.50' r FM
FM Fm
�FM FM
FM /
5.50' @ FM --- FM FM FM FM
JFM FM FM—.,
FM FLUSHING ASSEMBLY (7YP)
FM FM
FM
FMB_ —
40.00'
FM
DI FW,
3IC SCALE
6 - 20 LL
—f1
i
I
—G G
i
4 INCH 0900 OR /4
SEWER LINE FROM HOUSE
NEW 1500 GAL. 2 COMPARTMENT
SEPTIC TANK, TOP OF TANK 70
B£ 5' BELOW FINISHED GRADE
SEE DETAIL FOR INSTALLATION
wd _J
1.5 INCH PVC SCH. 40
FROM DISCHARGE ASSEMBLY
TO ADV VALVE
SEP77C ENVELOPE & —
10' PROPER7Y OFFSET
SYSTEM 2
__- 89
GM I Duckworth Residence OWTS
shall, s!, P00
9¢,c081601 Pitkin County, Colorado
System 2
Design Layout
N
aacnRPAW RELD NOTES
x
I. ASSORPAaJ FIFLAS 70 SE A SAND
AN PE
AND SOY REGULATIONS IFF)rNCMS.
E
2. FIELD )O
nmy`N VQ IIIO
3
FOLLOW R DRAED GRADE
SURFACE 70 ALLOW FOR ORVANGE AS
CH4MBERED DESIGN CRRERN
Digging Specs
Invert
Dimensions
Net Capacity
SHOWN ON PLANS
OESIGN PLOW - 600
°i
13' Long x 6" Wide
/n/et
Out/et
Length
Width
Neighl
/n/et Side
Out/et Side
Total
3. EFFLUEM LINE FROM PUMP 70 AOV 10
PERCOLIT ON RITE a 74 MPI
a
BE 1.5' ^v Sao 4a EiFLUENT UNEs FORM
AREA— 600/.95- 632 SF
0
56" below in/et inverf
56"
73'
132"
6B"
91"
1,002 go//ans
503 go//ons
1,505 go//ons
'DV TO FAEZD TO BE I' PVC SCH 40.
S4ND FILTER SPEL^IFK'
Net Weight
',NeeMASTM
'N"
ALATERAL LINES TO BE 1' PVC SCH. 40.
3/16 DRILL HOLES 70 BE LOCATED EVERY 3'
NUMBER OF ZONES — 3
a
Lid Tank
Total
c-f2lTspee
bactudLrigalst4-Wforhvalent
AT THE 12.,00 POSRTON AND 3/16' DRLLL
NUMBER OF LAWRALS —
3600 /bs
11,800 /bs
14,980 /bs
connectors
HOLES AT THE 6.00 POSITION 2' FROM THE
LENGTH OF tAnM4S —
4000 psi concrete
START AND END OF THE LATERAL. ORIRCE
D/MENIIONS 1B FT X. 40
O
Delivered complete with internal piping
SHIELDS MOOEZ / OS 100 TO BE 1NSTALLEO
h
OVER ALL UPWARD DRILL HOLES
TOTAL AREA a 720 SF
5. FLUSHING ASSEMBLIES TO BE INSTALLED
AT THE END OF EACH LATERAL Sff DETAIL
Gw0 I Duckworth Residence OWTS
s 200
9,co916101 Pilkin County, Colorado
System 2
Details
lob No. 2005521.001
L
Of 0
Drown by: da
Octe: 10.24.12
aC: -x Dr,
N
W
FAL
r, oe Ls'
^1TMISrm GRADE
Pke stp
,X FPr AOWr.
W/ PLUG
LYE Bar
�BUl VALVE
IPSC mm
)LOAD SXEEP
DER fim
FLUMING ASSEMBLY
Aar W .4sVE
UWAW AREAS I MW ANFAS
"W roro YOX VOffOExWlYmWEa PREtELnrAD H4DPGL cnBancr
ro str ANX OPY O'OVS
AWM rW B' ALL S ES RPE
1. OEMM M 4WW ro BE CLASS B ABC
OR OWW AaERXt APPXV6£D BY O WNEEle
PIPE DETAIL
iwr m m
ilex Pumping System for Cold Weather Applications (cw sti.
Scale: V = 2' Control Panel Top View ftii8)
Model MVP-DAX 1 ROk(IBA Duplex PImvkv ayetem
Slope Ground /
Model FL 240*AW \ Away from Raiser
PVC Ear
Tank Adapter
(Camcr BoBed)
Model PRTA 24 BI}KR
Inlet Tee
Patents If 4,439,323 & 5,492,635
Foreign Portents May Apply
02006, Orenco Systems, Inc.
Conduit to
Control Panel
CondIM Beal-J
Model SECS ID0
PVC Stake Box
w/Cord Grips
/ Model 130D(4
rEffluent
w Oasketed Ltd with
Steel sow
L 30 (34
fV 125Aeee -0®(?J
ar with CTromi neNe)
R 3060
Gravel Backfill
Hole HV CW 125 KIT (2)
Discharge (below frost line)
wssswsr� -
fTW: Adapter
(Cast or SoMeoA
Model PRTA 30 BD-M
Level Control
Float Assembly
Model MF 3A YP,B,R-3W
Flou fad=
Vault Inlet Portz
Filter Cenddge
Oren» Effluent Rap (2)
ModelPFOOOStl
ftbAW Pulp Vault
Model PVU 89-1819-L
# Pea Gravel Backfill Recommended to Help Prevent Frost Heave
*# Optional Drain Hole for Drain Back of Transport Line or Bury Below Frost Line
_VEEP
rep 4yf\ )�
■
SAW Ctff — PLUS
PVC aZ4AVUr W9 OR
OBSVM
tAl
■ criMY
f:.�O)tl■
I' uL v ,
Is
un
sues,■ ■ ■ UNAS
CLEAN —OUT DETAIL
AW 7D SCALE
Orenco Systemsp
COOK Atli
Incaryon"
1. WIDIUDe SHILL OOIOeWr ro ALL WM CWOY TEALN DOWMOVr
REGUTAMM ALL COAP ARUff OF NE Wear W45TE1NI70 S1s7EW
IN AM NIEW
(OM .SHILL ANEr AFROIS E REmAATkne.
&81181q 01®Opl
t Ne arms SAOL BE AVSDNIED W ALCAWQW WN star
AFEWMIIAN Y AND ANK/ 40RQIIRS ALn'NIOIDIfO "M SVWSORBXNB aF
9709-Wlt
C41PPOWS dt UMMUS B!L ROr AE NLONED 0171WT RE NM77FN
A 100101L Or DfE OESOV ENpA OSMM 901L FFOMOE Aar MM
S OWNS NIvEN RLOUMM SIABSONOOVI
TOLL FR8
S NE OWN RUD AWA SNIXAD BE FROWYED 1X W LCNPIL7 At
IflICY/!Ae rAViX SAVOLO BE KIM OF WE OBIW Ma ~ ?R&CU
AW
Sea R m �AIa 9ShOULDW rW R130 ALLOW ON
/ff WCERER,
18,111IM
A ALL PW FW co wFCnOXS swL fir SOLM7 #a= LWLESS
(641) IN of a
OIAOMW sPECsrm
FAISM
S ALL m3em YAL1£ BaXES 9wL OMM 2 MW AMW SUPPOLIAOM
(eft) 40-2EI
MWEv GRIPE sox &rAu LE attar UP Attaw am AAD SLOPED
ANAY LADY MW Ar A Ee' WN SLQ^&- SLpaE ro &In4Yr.
B SENOR POE AAD EFFLUENT PIPE S WU BE PNOWXY SEVED PER
V E TRWCH DEW PROMED.
F. RE NJ 4r BE ME AFSIQ 9CNY OY BE OIIAER.
a SSIXC TAHr A559/BLES &WL W C•ONSRCCED ANW? TXWT 72
ASSLWE AO GROLNO OR 57aw owT wu EFFECT amen a ttasm
7. PLAp'ONI SMM SA4L MW A IXVD NEAVO? OSC7VNCE' ASSMIGUY.
SEEP 1ALEW COW NEINW MSCNKea• ASSIMMY "a OWN &Wr
WTO SEPTIC rAHC
S a/asWW ASSBaY MUL MW A A@'tiHAELr rWA'/I ACCESS$E
MOV WOrOO LEVEL FOR ROW T'>tP' EALT7R7Yr.
A FWP SYSW SWL. MOVE 4 ROIr swnwm AN 4w" ILCNr. m
2W7' FLOIr. AW A hM A O LOW 10419? "M
S ALOIIS SHILL fir SET ro OaAW A 101 a4fLOY DOSE (ro-
S0AW1DV FDA SSTEW 1) AND ( W SEPARIDOV ILw SY57EW 2) ro
BE OSAW AlMa
e FLfar TREE MN" AND RLIW MME M&L EXTEND ro A AMA
OEPN CP lY A06 BELOW W RW Or NE TAW RSW
7. ARSTA(LER SWILL RAWM ANO NSRU AN EAIEAIW. SVAE BaA
BALL MEZVEM &Y4L BE COMPLETED elm, M L SW WAIUMOO,
CuwAOL PA&Et•
r. AVSIAAER SN4U PROW A ASA IX RI7W CaVIR& PANEL
T. L'ONMULS AND At~ S64L BE L5W PER rA 501
NDW—TD—EPS—HV-02 .x COW104CICw sate COVWXT OWX? AND/Lw GDOW CaVM a7OR
Rev. 3.0 (03/06) Rw LOOMON BP CONMOL PANEL CONWOL PAva vwLL w 4aPN1m
OV NE EYTF7mw CV' DE mXL" OR NflWf WAZYM CLVIRpfO STAND
XMW Sravr CF DE RESM1711 F AaMW SYSTM
A COMMAL AWES MAU BE AV Wm AT A CONWM7 hWff 10
ALLOW ACCESS ANO AAI00BOUAE
SEEN/NEL. SE LOrAW SIGN RaT rW ALARM CAN BE RF"Y
AAV
DIREC77ON
OF
fz0W
w��
Pump Selection for a Pressurized System - Single Family Residence Project
Duckworth OWTS / System 1
Parameters
Discharge Assembly Size
Transport Length Before Valve
Transport Pipe Class
Transport Line Size
Distributing Valve Model
Transport Length After Valve
Transport Pipe Class
Transport Pipe Size
Max Elevation Lift
Manifold Length
Manifold Pipe Class
Manifold Pipe Size
Number of Laterals per Cell
Lateral Length
Lateral Pipe Class
Lateral Pipe Size
Orifice Size
Orifice Spacing
Residual Head
Flow Meter
'Add-on' Friction Losses
1.25
12
40
1.50
6404
40.9
40
1.00
12
6
40
1.00
12
30
40
1.00
3/16
3
5
None
0
inches
feet
inches
feet
inches
feet
feet
inches
feet
inches
inches
feet
feet
inches
feet
Calculations
Minimum Flow Rate per Orifice
Number of Orifices per Zone
Total Flow Rate per Zone
Number of Laterals per Zone
% Flow Differential 1st/Last Orifice
Transport Velocity Before Valve
Transport Velocity After Valve
0.97
33
32.7
3
6.2
5.2
12.2
gpm
gpm
%
fps
fps
Frictional Head Losses
Loss through Discharge
Loss in Transport Before Valve
Loss through Valve
Loss in Transport after Valve
Loss in Manifold
Loss in Laterals
Loss through Flowmeter
'Add-on' Friction Losses
7.5
0.7
7.8
20.2
0.8
0.8
0.0
0.0
feet
feet
feet
feet
feet
feet
feet
feet
Pipe Volumes
Vol of Transport Line Before Valve
Vol of Transport Line After Valve
Vol of Manifold
Vol of Laterals per Zone
Total Vol Before Valve
Total Vol After Valve
1.3
1.8
0.3
4.0
1.3
6.1
gals
gals
gals
gals
gals
gals
Minimum Pump Requirements
Design Flow Rate
Total Dynamic Head
32.7
54.9
gpm
feet
0 5 10 15 20 25 30 35 40
0
50
100
150
200
250
300
Net Discharge (gpm)
PumpData
PF3005 High Head Effluent Pump
30 GPM, 1/2HP
115/230V 1Ø 60Hz, 200V 3Ø 60Hz
Legend
System Curve:
Pump Curve:
Pump Optimal Range:
Operating Point:
Design Point: