HomeMy WebLinkAboutPitkin.EH.273503202001 (2016)Pitkin County Environmental Health Department
Onsite Wastewater Treatment System (OWTS) USE PERMIT
Permit for Continued Use of an Existing OWTS
76 Service Center Road, Aspen, CO 81611
Phone: 970-920-5070 Fax: 970-920-5077
www.aspenpitkin.com/EHNR
Parcel ID #: 2735-032-02-001
OWTS Use Permit #: 0069.2016.POWU
Date Issued: 12/21/2016
Issued By: Kurt Dahl
Expiration Date: 12/21/2017
Owner(s): Christianna Sep. Prop. Tr.
Property Address: 1044 Owl Creek Rd
Legal Description:
Licensed Inspector: Carla Ostberg
Inspection Date(s): 11/16/2016
SYSTEM INFORMATION
Components Type Capacity/Size
Primary Treatment Unit Concrete single-compartment septic
tank
1500 gallons
Secondary Treatment Unit Concrete two-compartment septic
tank with pump in second
compartment
1500 gallons
Absorption Area Gravelless soil treatment area
(trenches)
72 chambers (1350 ft2)
Other System Components Distribution box
In use at the time of the inspection. Not in use at the time of the inspection.*
*If the OWTS was not in use at the time of the inspection, it is recommended that the system be re-evaluated when it is in use for a more accurate
evaluation of the system.
System Records:
Permit #: 01051 Date of Issuance: 08/13/2001 Date of Final Approval: 7/15/2002
# of Bedrooms or fixtures served by OWTS: The system is sized to serve 6 bedrooms. This is a duplex with 3 bedrooms in unit 1 and
3 bedrooms in unit 2.
Operational Status: The inspector indicates the system is functioning properly and there is no evidence of failure.
Inspector Recommendations: Add handles to the effluent filter and float tree, bring distribution box access to grade.
Department Recommendations: Annual maintenance and inspector recommendations.
Issuance of this OWTS Use Permit is based solely on the conditions observed and reported by the inspector to the Department on the date of the inspection(s) and
on Department records at the time of permitting. The issuance of this permit does not constitute a guarantee, warranty, or representation by the Department
that the system will operate properly or will not fail or that the system will not be subject to future enforcement action to correct non-compliant conditions.
Estimated capacity of the system has been listed on the permit and we recommend that you monitor and/or meter water use to prevent overuse and possible
failure.
0069.2016.POWU
CBO Inc.
33 Four Wheel Drive Road
Carbondale, CO 81623
cell) 970-309-5259 office) 970-704-0484
carla.ostberg@gmail.com
November 30, 2016
Dina Erickson
dina.erickson@engelvoelkers.com
Onsite Wastewater Treatment System (OWTS) Use Permit Inspection
1044 Owl Creek Road
Pitkin County, Colorado
Dina,
As requested, CBO Inc. performed an Onsite W astewater Treatment System (OWTS) Use Permit
inspection at 1044 Owl Creek Road, Aspen, Colorado on November 16, 2016. The legal description of
the property is Unit 1, Badger Hollow Townhomes.
The permit and record drawing was provided by Pitkin County Environmental Health Department (Parcel
ID #2735-032-02-001). The subject OWTS consists of a 1500-gallon, single-compartment concrete
septic tank followed by a 1500-gallon, two-compartment septic tank with an Orenco® Biotube Pump Vault
and duplexing pump system in the second compartment of the septic tank. Effluent is pumped to a
distribution box and then to six gravelless chamber trenches, each with 12 ‘Standard’ Infiltrator®
chambers for a total of 72 chambers and 1350 square feet of infiltrative area. Individual Sewage
Disposal System Permit 01051 documents this system. The system was sized to accommodate 6
bedrooms. The permit received final approval on July 15, 2002.
The septic tanks are located to the north of the eastern most duplex. The outlet side of the first septic
tank in series was accessible from grade at the time of our inspection. The septic tank had an
accumulation of solids was at approximately 30% of the tank capacity and warranted pumping. This
septic tank was pumped by Altitude Septic on November 29, 2016. The inlet side of the septic tank was
uncovered for the pumping and was only a few inches below grade. There are two inlets into the septic
tank; one from each duplex. The outlet tee was present in the septic tank and liquid levels in the tank
were normal prior to pumping.
Only the pump chamber of the second septic tank in the series was accessible at the time of the
inspection. The filter and float tree do not have a handle extension making removal of either very difficult.
Operation of the float pumps required entering the manway. We recommend adding a handle
extension to both the effluent filter and the float tree. We tested the pumps and the alarm by lifting
the floats and all were operational. The control panel for the pumps is located on the northern wall of the
east duplex. Note the different pump run times on the duplexing pump system (photo below). We do
know that a bad float was replaced in 2012 at the time of the last inspection.
Effluent is pumped to a distribution box, which was not accessible from grade at the time of our
inspection. We were no able to inspect this component. We recommend locating and bringing the
distribution box to grade for future inspection and monitoring.
We walked the approximate soil treatment area (STA) and inspection ports are present at the end of
each trench. All ports were dry at the time of our inspection. We walked the entire area and found no
evidence of surface saturation or failure at the time of our inspection. This evaluation is not a guarantee
of future system performance. This inspection is good for one year.
0069.2016.POWU
Recommendations:
• Clean effluent filter annually, or as needed.
• We recommend adding a handle extension to both the effluent filter and the float tree.
• Locate distribution box and bring to grade.
This report and a completed OWTS Use Permit Application must be submitted to the Pitkin County
Environmental Health Department. Applications may be submitted to Pitkin County Environmental Health
Department electronically. The following are links to the required OWTS Use Permit Application and
Checklist.
Application: http://www.pitkincounty.com/DocumentCenter/Home/View/621
Application Checklist: http://www.pitkincounty.com/DocumentCenter/Home/View/620
Also enclosed are instructions on how to apply for an OWTS Use Permit electronically. All questions
regarding permit submission can be directed to Pitkin County Environmental Health Department, 970-920-
5070.
Disclaimer: This inspection is intended only as an evaluation of the present condition of the OWTS
based upon what was observed and the Licensed Inspector’s expertise in onsite wastewater technology.
The Inspector has not been retained to warrant or guarantee the proper functioning of the system for any
period of time in the future. Because of numerous factors which may affect the operation of an OWTS,
as well as the inability of the Inspector to supervise or monitor the use or maintenance of this OWTS, this
report shall not be construed as a warranty by the Inspector that the system will function properly for any
particular prospective buyer, and the Inspector disclaims any warranty, either expressed or implied,
arising from the inspection of the OWTS or this report. The evaluation does not ascertain the impact the
system is having on groundwater.
Please call with questions.
Sincerely,
Carla Ostberg, MPH, REHS
NAWT Certified Inspector
Certification # 11044ITC Exp. April 2018
0069.2016.POWU
Arrows indicate control panel, clean out, inlet side of 1st tank, pump chamber of 2nd tank
Inlet tee from one duplex Inlet tee from other duplex
Outlet tee of first tank
0069.2016.POWU
Control panel
Counters (note different run times)
Pump chamber (recommend handle extension on float tree and filter
0069.2016.POWU
Note splice box in manway
STA (looking north) inspection pots at the end of each row
Note lack of vegetation in areas
Inspection ports This alarm does not appear to be associated with the OWTS
0069.2016.POWU
Owner's Name:
Address:
Parcel Number:
Inspection Date:
Pitkin County Systems Inspector License Number:
QUESTIONS FOR PROPERTY OWNER PRIOR TO INSPECTION:
Is the home currently occupied?YES NO
If NO, how long has the home been vacant?
How many bedrooms are in the home?
RECORDS:
Were system records available from Pitkin County?YES NO
If YES:Permit number: ___________
Date of Final Approval: _________
# of bedrooms permitted: ___________
Was an as-built drawing available?YES NO
Is the as-built drawing accurate? YES NO
If NO:
SITE CONDITIONS:
Proper grading, no evidence of erosion?PASS FAIL
Improper vegetative cover?NO YES
Evidence of compaction such as heavy machinery or livestock?NO YES
Improper discharges such as straight pipes?PASS FAIL
Evidence of high ground water?NO YES
Snow cover present?NO YES
Any question marked FAIL will require correction before an OWTS Use permit is issued.
If secondary treatment is used, who is the
maintenance provider?
Complete a drawing of the system on last page of this form as accurately as
possible.
Email:
Inspector's Name:
Business Name:
A copy of this inspection report will be remitted to Pitkin County Environmental Health Department by
the Licensed Systems Inspector within 60 days of the inspection regardless of whether the system
passes or fails.
Onsite Wastewater Treatment Systems (OWTS) Use
Permit Inspection Form
Inspection form for continued use of an existing OWTS
Website: www.aspenpitkin.com/ehnr
Pitkin County Environmental Health Department
76 Service Center Rd, Aspen, CO 81611
Phone: 970-920-5070 Fax: 970-920-5374
Phone Number
Page 1
Christianna Seidel 1999 Property Trust
1044 Owl Creek Road
Aspen, CO
2735-032-02-001
11/16/16
Carla Ostberg
CBO Inc.
970-309-5259
carla.ostberg@gmail.com
017
3
N/A
01501
7/15/2002
6 total (3 bedrooms each duplex)
OWTS Use Permit 0016.2012.POWU
Issued 6/14/12
0069.2016.POWU
TANK:
Tank capacity gallons gallons gallons
Tank material
# of compartments
Date of last pumping
Lids/risers in good condition PASS FAIL PASS FAIL PASS FAIL
Risers to grade YES NO YES NO YES NO
Riser height
Riser condition/watertightness
Inlet sanitary T/baffle PASS PASS FAIL PASS FAIL
Outlet sanitary T/baffle PASS FAIL PASS FAIL PASS FAIL
Effluent filter (if part of design)
Condition of tank material PASS FAIL PASS FAIL PASS FAIL
Tank was pumped for inspection YES NO YES NO YES NO
If YES, list the pumping company
If NO, when was the last pumping
Scum level (1st compartment)inches inches inches
Sludge level (1st compartment)inches inches inches
Scum level (2nd compartment)inches inches inches
Sludge level (2nd compartment)inches inches inches
Backflow (if pumped)PASS FAIL PASS FAIL PASS FAIL
Midtank baffle
Watertightness PASS FAIL PASS FAIL PASS FAIL
PUMPS/DOSING SIPHONS:
Is a pump or dosing siphon present?YES NO
If YES, is the pump/dosing siphon functioning properly?PASS FAIL
Does the pump/wiring/dosing siphon appear to be in good condition?PASS FAIL
Is the high water alarm working, both visible and audible?PASS FAIL
SECONDARY TREATMENT:
Is a secondary treatment unit present?YES NO UNKNOWN
If YES, does the unit appear to be in good working condition?YES NO
Does the owner have a current maintenance contract for the unit?YES NO UNKNOWN
Maintenance Provider:_______________________________________Phone:________________________
ABSORBTION AREA:
Effluent surfacing?PASS FAIL
Evidence of past surfacing?NO YES
Surface dampness?NO YES
Excessive odors?NO YES
Field location verified by observation ports or probing:Ports Probing
Liquid in observation port?NO YES
If YES, record depth:inches
Distribution Box or ADV part of original design?YES NO UNKNOWN
If YES, is it accessible from grade?YES NO
Is it level and in good condition?PASS FAIL
If there is no maintenance contract, a contract must be in place prior to occupancy of the home. A
copy of the contract must be submitted to Pitkin County Environmental Health Department.
PASS FAIL N/A
PASS FAIL N/A PASS FAIL N/A PASS FAIL N/A
Tank 1 Tank 2 Tank 3
PASS FAIL N/A PASS FAIL N/A
Page 2
1500 1500
concrete concrete
1 2
2012
4'4'within 8" of
grade ok
pumped
after
inspection Altitude Septic
minimal
ok
n/a
0069.2016.POWU
Any problems with the system that were not addressed in the inspection checklist?
Please list any recommendations for the continued use of the system:
Were any repairs done as a result of this inspection?NO YES
If YES, please describe the repairs.
Licensed Systems Inspector Signature:
Additional Notes:
To the best of my knowledge and training, the information collected in this inspection is accurate as of
__________________, 20____.
Clearly label any pictures and attach them to this form.
Page 3
Tank alert XT associated with Rhombus pump light ON. This alert does not appear to be
associated with the effluent pump for the septic, which is an Orenco
clean filter annually, or as needed
add handle extension to filter and float tree in pump chamber of 2nd tank
November 30 16
pump tested from floats - operating properly
alarm tested and functional - lifted high water float
0069.2016.POWU
feet
meters
300
100
0069.2016.POWU
832‐R‐13‐002
0069.2016.POWU
0069.2016.POWU